16.7 Hz - The Missing Link?
|
|
- Heidi Wetzel
- vor 6 Jahren
- Abrufe
Transkript
1 16.7 Hz - The Missing Link? Prof. István Erlich University of Duisburg-Essen Bremen, January 2014
2 Current Concept 2
3 Current Concept Offshore Onshore WP1 33 kv AC, 50 Hz WP-Plattform WP-Plattform 150 kv AC, 50 Hz HVDC-Plattform 50 Hz DC 1000 MW 300 kv DC DC 50 Hz 400 kv AC WP2 Separate platform for each wind farm plus one additional HVDC Platform, both offshore 150 kv AC for wind farm connections voltage too low for considerable power transmission Converter technique is located offshore reliability concerns 3
4 Alternative Concept 16⅔ Hz Offshore Onshore WP-Plattform WP MW 16 2/3 Hz 50 Hz 400 kv AC 33 kv AC, 16 2/3 Hz WP2 WP3 WP-Plattform WP-Plattform 220 kv AC, 16 2/3 Hz 220 kv AC, 16 2/3 Hz MW MW 16 2/3 Hz 50 Hz 16 2/3 Hz 50 Hz 400 kv AC 400 kv AC 220 kv AC cable for power transmission to onshore 220 kv AC suitable for a mashed North Sea grid Separate platform for each wind farm but no need for HVDC platform No converter offshore 4
5 Cable Losses at Low Frequency Losses at I n_50hz =2483 A 70 W/m P c ~ P s P d P P c Hz 16,7 Hz 1 Hz 5
6 Alternative Concept 16⅔ Hz Converter onshore: Converter is not separated in offshore and onshore but back-to-back Not affected by sea climate Maintenance fast and to lower costs possible Mashed offshore grid easy to establish Quelle: Siemens 6
7 Wind Turbines Full rated WT Type 4 DFIG Type 3 Speed control Pitch and Power GB CR Speed control Pitch and Power GB ASG P ref SG/ ASG P ref MSC control P Q,cos,VG Thru fast current control MSC C MSC control VT MSC C CH LSC control U DC (Q,cos,V G ) LSC CH L LSC V G LSC control P VT U DC Q,cos,VG Thru fast current control L VG Change to 16⅔ Hz is difficult, 16⅔ Hz DFIG is too heavy Change to 16⅔ Hz is easily accomplished 7
8 16⅔ - 50 Hz Converter Already developed for single phase Example Datteln 50 Hz side: 4x103 MW With overload: 138 MW Nominal: 413 MW 103 (138) MW unit 8
9 245 kv Cable 245 kv Submarine Cable 1200 mm 2 Cu/RM 245 kv three phase XLPE submarine cable up to 2000 mm 2 Al and 1600 mm 2 Cu are available or can be built 9
10 245 kv Cable 245 kv Submarine Cables 2000 mm 2 Al/RE 1200 mm2 Cu/RM Parameter 50 Hz 16⅔ Hz 50 Hz 16⅔ Hz I max / ka (1.5) (1.5 S n /MVA R /m /km L /mh/km X /m /km C /nf/km G /ns/km
11 Calculation of Transmission Capacity Wind Farm P Wind Q Wind Shunt Reactor X R Offshore Cable, 100 sections Shunt Reactor X R P Grid Q Grid Onshore Grid Shunt reactors are calculated for full compensation of the cable 1 under no load conditions X R 2 2 f C Example: 1200 mm 2 Cu/RM Cable, 400 km distance ' cable l P Wind 617 MW Q Wind 0 Mvar 1.7 ka Voltage 245 kv P Grid 561 MW Q Grid 94 Mvar Hotspot I=Imax=1600 A Current Distance
12 Calculation of Transmission Capacity Wind Farm P Wind Q Wind Shunt Reactor X R Offshore Cable, 100 sections Shunt Reactor X R P Grid Q Grid Onshore Grid Shunt reactors are calculated for full compensation of the cable 1 under no load conditions X R 2 2 f C Example: 1200 mm 2 Cu/RM Cable, 400 km distance ' cable l P Wind 643 MW Q Wind 53 Mvar 1.7 ka Voltage 245 kv P Grid 584 MW Q Grid 53 Mvar Hotspot I=Imax=1600 A Current Distance 12
13 Calculation of Transmission Capacity Wind Farm P Wind Q Wind Shunt Reactor X R Offshore Cable, 100 sections Shunt Reactor X R P Grid Q Grid Onshore Grid 1200 mm 2 Cu/RM Cable, Imax=1500 A, 400 km distance Var demand supplied solely from the grid side Transmission Capacity: P Wind 589 MW P Loss 8.1% P Wind 589 MW Q Wind 0 Mvar 1.7 ka 1.6 Hotspot I=Imax=1500 A Voltage 245 kv 241 P Grid 541 MW Q Grid -84 Mvar Current Distance 13
14 Calculation of Transmission Capacity Wind Farm P Wind Q Wind Shunt Reactor X R Offshore Cable, 100 sections Shunt Reactor X R P Grid Q Grid Onshore Grid 1200 mm 2 Cu/RM Cable, Imax=1500 A, 400 km distance Var demand distributed equally to both ends Transmission Capacity: P Wind 604 MW P Loss 8.4% P Wind 604 MW Q Wind -45 Mvar 1.7 ka Hotspot I=Imax=1500 A Voltage 250 kv P Grid 553 MW Q Grid -45 Mvar Current Distance
15 Calculation of Transmission Capacity Wind Farm P Wind Q Wind Shunt Reactor X R Offshore Cable, 100 sections Shunt Reactor X R P Grid Q Grid Onshore Grid 1200 mm 2 Cu/RM Cable, Imax=1500 A, 400 km distance optimized operation for max. active power transmission Transmission Capacity: P Wind 610 MW P Loss 8.5% P Wind 610 MW Q Wind -58 Mvar 1.7 ka U=Umax=245 kv Hotspot I=Imax=1500 A Voltage Hotspot I=Imax=1500 A 250 kv P Grid 558 MW Q Grid -34 Mvar Current Distance 15
16 Compensation Demand Qc at both ends (Mvar) Transmission Characteristic 245 kv Submarine Cable 2000 mm 2 Al/RE Voltage and voltage angle transmission of 600 MW over 400 km Compensation demand 0 km Voltage offshore 1.2 V real in p.u Voltage onshore 400 km Grid PCC Q c Submarine Cable Q c Offshore Wind PP 9.56 deg Hz 16,7Hz V imag in p.u Cable Length (km) 16
17 Hypothetic Nord Sea Grid Meshed North Sea Grid with 16⅔ Hz at 220 kv level would be possible! 17
18 Power Flow in the North Sea Grid Assumed total generation power: 5000 MW Acceptable voltage drops Voltage angle differences are small Losses are acceptable 18
19 16⅔ Hz Transformer Experience in building 16⅔ transformers are available Weight is about 2x more than that of 50 Hz transformers 16⅔ Hz Transformer, 15 MVA; 120/17,25 kv, ONAN-Hermetik; Ii0 (Quelle: Alstrom) 19
20 Transmission Capacity of 400 kv Overhead Lines 3000 MW Power Transmission Capacity Hz 16⅔ Hz length (km) Conductor: 4xAl/St 550/70 R = 0,01315 Ohm/km ; X = 0,26 Ohm/km ; C = 0,014 F/km I max =4080 A 20
21 Transmission Capacity of 500 kv Overhead Lines 3800 MW 3400 Power Transmission Capacity Hz 16⅔ Hz length (km) Conductor: 4xAl/St 550/70 R = 0,01315 Ohm/km ; X = 0,26 Ohm/km ; C = 0,014 F/km I max =4080 A 21
22 Dynamic Simulation P + jq P + jq 16.7 Hz Offshore Grid R16.7Hz L16.7Hz MMC 300 km - B1 Submarine Cable B2 B3 50 Hz Utility Grid Active Power Controller + Reactive Power Controller 16.7Hz Grid Side Converter (GSC) Udc MMC 50Hz Grid Side Converter (GSC) L50Hz R50Hz DC Voltage Controller (Udcref = 400 kv) + Reactive Power Controller 16.7 Hz Offshore Grid Onshore Frequency Converter + 50 Hz Grid Active Power(MW) Reactive Power (Mvar) MW 80 Mvar 400 MW Active Power Pref Rective Power Qref 50 Mvar Reactive Power (Mvar) MW Time (s) (a) Reference Power Flow in 16.7 Hz Grid Time (s) (b) Reference Reactive Power Flow in 50 Hz Grid
23 Simulation Results 16.7 Hz side Sending End
24 Simulation Results 50 Hz side
25 Conclusions The integration of offshore wind farms by three phase 16⅔ Hz technology and setting up a 16⅔ Hz offshore grid is a favorable alternative to DC links Converter are only onshore, easy to acces and not affected by serious weather conditions No need for HVDC platform offshore Offshore are only approved technologies like transformer and switch gears Due to meshed 220 kv grid (n-1) security is possible Extention to 400 kv (500 kv) onshore overlay grid is possible by 16⅔- Hz technology 25
26 Thank you for your attention! Thank you for your attention! 26
Asynchronous Generators
Asynchronous Generators Source: ABB 1/21 2. Asynchronous Generators 1. Induction generator with squirrel cage rotor 2. Induction generator with woed rotor Source: electricaleasy.com 2/21 2.1. Induction
MehrNeue Alternativen zur Kurzschlussstrombegrenzung
Neue Alternativen zur Kurzschlussstrombegrenzung Katrin Bäuml 12. Symposium Energieinovation TU Graz Februar 2012 Inhalt Entwicklung der Netzstrukturen Vergleich unterschiedlicher Strombegrenzer Neue Begrenzertechnologien
Mehra new line of steam sterilizers
a new line of steam sterilizers ticheeasy to use and high consumption savings multifunction display controlled by micro-processor double and patented motor-operated closure stainless steel chamber without
MehrSimulation of a Battery Electric Vehicle
Simulation of a Battery Electric Vehicle M. Auer, T. Kuthada, N. Widdecke, J. Wiedemann IVK/FKFS University of Stuttgart 1 2.1.214 Markus Auer Agenda Motivation Thermal Management for BEV Simulation Model
MehrWakefield computation of PETRAIII taper section Laura Lünzer
Wakefield computation of PETRAIII taper section Laura Lünzer 16. Dezember 2011 TU Darmstadt Fachbereich 18 Institut Theorie Elektromagnetischer Felder Laura Lünzer Geometry of tapered structure Undulator
MehrGIS-based Mapping Tool for Urban Energy Demand
GIS-based Mapping Tool for Urban Energy Demand Building Services, Mechanical and Building Industry Days Conference Johannes Dorfner Debrecen, 14 October 2011 Outline 1. Motivation 2. Method 3. Result 4.
MehrChemical heat storage using Na-leach
Hilfe2 Materials Science & Technology Chemical heat storage using Na-leach Robert Weber Empa, Material Science and Technology Building Technologies Laboratory CH 8600 Dübendorf Folie 1 Hilfe2 Diese Folie
MehrMeteorological measurements at the Offshore Platform FINO 2 - new insights -
FINO 2011 Conference May 11 th 2011, Hamburg, Germany Meteorological measurements at the Offshore Platform FINO 2 - new insights - Dipl.-Geoök. Stefan Müller, Dipl.-Ing Joachim Schwabe Content 1. FINO
MehrEingebettete Taktübertragung auf Speicherbussen
Eingebettete Taktübertragung auf Speicherbussen Johannes Reichart Workshop Hochgeschwindigkeitsschnittstellen Stuttgart, 07.11.2008 Unterstützt durch: Qimonda AG, München Institut für Prof. Elektrische
MehrInternationale Energiewirtschaftstagung TU Wien 2015
Internationale Energiewirtschaftstagung TU Wien 2015 Techno-economic study of measures to increase the flexibility of decentralized cogeneration plants on a German chemical company Luis Plascencia, Dr.
MehrPilot Project Biogas-powered Micro-gas-turbine
1/18 Pilot Project Biogas-powered Micro-gas-turbine Supported by the Hessischen Ministerium für Wirtschaft, Verkehr und Landesentwicklung Speaker Details 2/18 Jan Müller Works at Institute of Solar Energy
MehrEin- und Ausgangsspannung 220-240V / Leistung: 800 VA / Abmessungen: 203 x 147 x 445mm / Gewicht: 20kg / Normenzertifikate: EN 60950, EN 60601-1
Produktinformationen Powervar ABCE800-22IEC USV POWERVAR Unterbrechungsfreier Strommanager Der neue Security One USM oder unterbrechungsfreier Strommanager, hat viele neue Funktionen zu bieten. Sie können
MehrPA-CONTROL CANopen Fehlerliste Ab Version 5.15 Ausgabe: 06/2008 Art.-Nr.:1082211. Technische Dokumentation
Technische Dokumentation PA-CONTROL CANopen Fehlerliste Ab Version 5.15 Ausgabe: 06/2008 Art.-Nr.:1082211 IEF Werner GmbH Wendelhofstr. 6 78120 Furtwangen Tel.: 07723/925-0 Fax: 07723/925-100 www.ief-werner.de
Mehr60 Jahre HVDC Weltweiter Rückblick der Entwicklung und Ausblick für Deutschland
Stefan Habild, ABB AG, Geschäftsbereichsleiter Grid Systems 09.04.2014 60 Jahre HVDC Weltweiter Rückblick der Entwicklung und Ausblick für Deutschland Uno Lamm - The Father of HVDC With ABB: 1927 1969
Mehrhigh potential insulating transformer Hochpotenzial- Trenntrafo bis 80 kv Potenzialtrennung up to 80 kv potential difference Tauscher Transformatoren
Hochpotenzial - Hochspannungs - Trenntransformatoren pri - sec und einer Leistung von 1 VA bis 3000 VA Isoliertrafo, Isolationstransformator Einsatzmöglichkeiten Hochspannungstrenntransformatoren werden
MehrAssumptions on Costs and Scenarios BERLIN, 01.03.2013
Cost optimal expansion of renewables in Germany Assumptions on Costs and Scenarios BERLIN, 01.03.2013 Assumptions on future investment costs per technology Assumptions on the investment cost of renewables
MehrRole of photovoltaics in the future energy mix: What comes after the current regulations?
Role of photovoltaics in the future energy mix: What comes after the current regulations? Hochschule für Technik und Wirtschaft HTW Berlin 2nd Inverter and PV System Technology Forum 2012 23 January 2012
MehrÜberspannungsschutz für Bauteile und Schaltungen mit Hilfe von TVS-Dioden. Circuits using TVS Diodes
Überspannungsschutz für Bauteile und Schaltungen mit Hilfe von TVS-Dioden Overvoltage Protection of Devices and Circuits using TVS Diodes Was ist eine TVS Diode? What is a TVS diode? I F V C V BR V WM
MehrCleanroom Fog Generators Volcano VP 12 + VP 18
Cleanroom Fog Generators Volcano VP 12 + VP 18 Description & Functional Principle (Piezo Technology) Cleanrooms are dynamic systems. People and goods are constantly in motion. Further installations, production
MehrTechnology for you. Media Solutions
Technology for you Media Solutions Media Units / Media Units Media Units Robuste Installationstechnik für jeden Klassenund Schulungsraum Robust installation technology for each class- and conference room
MehrGrid Integration of Photovoltaics Technical solutions status quo and prospect
Martin Baart, Business Development Manager Microgrids & Renewable Integration, ABB AG, June 20, 2013 Grid Integration of Photovoltaics Technical solutions status quo and prospect PV Integration Current
Mehrdrawbar eye series 2010
drawbar eye series 2010 directive 94/20/EG / class S DIN 74054-40A / material St52-3 (no. 1.0570) / with bush 40 mm parameters for centre-axle trailer s ṣhaft cross section order no H x B mm length A mm
MehrGRIPS - GIS basiertes Risikoanalyse-, Informations- und Planungssystem
GRIPS - GIS basiertes Risikoanalyse-, Informations- und Planungssystem GIS based risk assessment and incident preparation system Gregor Lämmel TU Berlin GRIPS joined research project TraffGo HT GmbH Rupprecht
MehrUWC 8801 / 8802 / 8803
Wandbedieneinheit Wall Panel UWC 8801 / 8802 / 8803 Bedienungsanleitung User Manual BDA V130601DE UWC 8801 Wandbedieneinheit Anschluss Vor dem Anschluss ist der UMM 8800 unbedingt auszuschalten. Die Übertragung
MehrStudienkomitee A2 Transformers. Martin A. Stössl Siemens AG Österreich Transformers Weiz
Studienkomitee A2 Transformers Martin A. Stössl Siemens AG Österreich Transformers Weiz A2 Working Groups - Themenschwerpunkte 1. Zuverlässigkeit A2.37 Tx reliability survey A2.40 Copper sulphide long-term
MehrShock pulse measurement principle
Shock pulse measurement principle a [m/s²] 4.0 3.5 3.0 Roller bearing signals in 36 khz range Natural sensor frequency = 36 khz 2.5 2.0 1.5 1.0 0.5 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0 350 360 370 380 390
MehrSolarfarming Switzerland/Canada
Solarfarming Switzerland/Canada Conversion of energy from the sun Components of solar systems Steps of solar cell production Types of solar cells and modules Features of solar inverters Photovoltaic, Biogas,
MehrCable specifications (see page 21) Cable specifications (see page 21)
Part No. Y-ConCable-1 4+2 Y-ConCable-2 4+0 for use with Y-Con series plugs, with 4 data and 2 power lines, with Y-Con series plugs, with 4 data lines, mit 4 Daten- und 2 Stromversorgungsleitungen, NICHT
MehrA closer look at the M/G/R PS model for TCP traffic
A closer look at the M/G/R PS model for TCP traffic July 23, 2001 Institute of Communication etworks Munich University of Technology 1 Outline Simulation Scenario Sojourn Time Formulas Investigated Scenarios
MehrKuhnke Technical Data. Contact Details
Kuhnke Technical Data The following page(s) are extracted from multi-page Kuhnke product catalogues or CDROMs and any page number shown is relevant to the original document. The PDF sheets here may have
MehrGeometrie und Bedeutung: Kap 5
: Kap 5 21. November 2011 Übersicht Der Begriff des Vektors Ähnlichkeits Distanzfunktionen für Vektoren Skalarprodukt Eukidische Distanz im R n What are vectors I Domininic: Maryl: Dollar Po Euro Yen 6
MehrGerman Norwegian Seminar on Hydro Power
German Norwegian Seminar on Hydro Power Oslo, November 16 th 2011 Hauptstrasse 6 99439 Wohlsborn Germany Phone +49 (0)3643 41502 17 Fax +49 (0)3643 41502 20 E-Mail info@kleinwasserkraft.de Web www.smallhydropower.de
MehrKraftwerk Berlin. Today, this formerly silenced Berlin power station is a vibrant place for exhibitions and events. A space resonating with energy.
Kraftwerk At the centre of, on the Köpenicker Straße, is the former power station Mitte a piece of s industrial history. Built approximately at the same time as the Wall during the years 1960-1964, its
MehrCONTROLLER RECEIVER REPEATER PAIRING SLIM CLIP
ANLEITUNGEN // INSTRUCTIONS CONTROLLER RECEIVER REPEATER PAIRING SLIM CLIP BEDIENUNGSANLEITUNG // INSTRUCTION MANUAL MONTAGEANLEITUNG // ASSEMBLY INSTRUCTION MONTAGEANLEITUNG // ASSEMBLY INSTRUCTION KOPPLUNG
MehrWegeventile EHF/EHP Sectional Valves
Wegeventile EHF/EHP Sectional Valves Technische Daten Technical Specifications Kenngrößen Parameters Nenndurchfluss (max. Durchfluss) Nominal flow rate (max. flow rate) Max. Druck max. pressure rate Max.
MehrSteca Electronics Services and products for an ecological future. 13th of June 2012 Christian Becker
Steca Electronics Services and products for an ecological future. 13th of June 2012 Christian Becker Brief overview over the company 2 This is Steca The philosophy of Steca Steca has long stood for ideas
MehrNetzausbaubedarf in Deutschland und den europäischen Nachbarländern: Eine Szenarienanalyse
DIW Berlin 05 April, 2013 Source: ECF (2010) Netzausbaubedarf in Deutschland und den europäischen Nachbarländern: Eine Szenarienanalyse Dipl.-Wi.-Ing. DIW Berlin - 0 - Agenda 1. Einleitung 2. Europas Infrastrukturbedarf
MehrMitglied der Leibniz-Gemeinschaft
Methods of research into dictionary use: online questionnaires Annette Klosa (Institut für Deutsche Sprache, Mannheim) 5. Arbeitstreffen Netzwerk Internetlexikografie, Leiden, 25./26. März 2013 Content
MehrPump Storage Requirements and Comparison with other Technologies
Pump Storage Requirements and Comparison with other Technologies Albert Ruprecht Institute of Fluid Mechanics and Hydraulic Machinery University of Stuttgart 1 Content Introduction Demand on pump storage
MehrJONATHAN JONA WISLER WHD.global
JONATHAN WISLER JONATHAN WISLER WHD.global CLOUD IS THE FUTURE By 2014, the personal cloud will replace the personal computer at the center of users' digital lives Gartner CLOUD TYPES SaaS IaaS PaaS
MehrThe impact of wind turbines on the behavior of the grid protection in consideration of the negative sequence interference
Presented at 0 3rd EEE PES SGT Europe, Berlin, Germany, October 4-7, 0 The impact of wind turbines on the behavior of the grid protection in consideration of the negative sequence interference Jörg Meyer,
MehrElektronische Identifikation und Vertrauensdienste für Europa
Brüssel/Berlin Elektronische Identifikation und Vertrauensdienste für Europa Wir wären dann soweit --- oder? Thomas Walloschke Director EMEIA Security Technology Office eidas REGULATION No 910/2014 0 eidas
Mehrp^db=`oj===pìééçêíáåñçêã~íáçå=
p^db=`oj===pìééçêíáåñçêã~íáçå= How to Disable User Account Control (UAC) in Windows Vista You are attempting to install or uninstall ACT! when Windows does not allow you access to needed files or folders.
MehrDatenblatt / Data sheet
Elektrische Kenndaten Eigenschaften / Electrical properties Höchstzulässige Werte / Maximum rated values Periodische Spitzensperrspannung repetitive peak reverse voltages Elektrische Eigenschaften Thermische
MehrEtherNet/IP Topology and Engineering MPx06/07/08VRS
EtherNet/IP Topology and Engineering MPx06/07/08VRS 3 1. Engineering via free EtherNet/IPTM-Port of a device on Bus from MPx07V10 2. Engineering via optional Industrial-Ethernet-Switch 3. Engineering via
MehrEnergieeffizienz und Erneuerbare Energien Programme der EZ -- ein Zwischenstand
Energieeffizienz und Erneuerbare Energien Programme der EZ -- ein Zwischenstand Climate Policy Capacity Building Seminar Kiew 07.10.04 Klaus Gihr Senior Project Manager Europe Department Was sind unsere
MehrProposal for Belt Anchorage Points
Proposal for Belt Anchorage Points Heiko Johannsen Johannes Holtz Page 1 NPACS Belt Anchorage Points Positions acquired based on car measurements Front seats In most rear position Rear seats Upper Fwd
MehrThe Integration of Renewable Energy Sources Into the Distribution Grid
The Integration of Renewable Energy Sources Into the Distribution Grid Türk-Alman Enerji İnovasyon Forumu 2013 20 ve 21 Kasım 2013 tarihlerinde Berlin de Dipl. Ing. H. Loew German Renewable Energy Federation
MehrHazards and measures against hazards by implementation of safe pneumatic circuits
Application of EN ISO 13849-1 in electro-pneumatic control systems Hazards and measures against hazards by implementation of safe pneumatic circuits These examples of switching circuits are offered free
MehrVDE Prüf- und Zertifizierungsinstitut Zeichengenehmigung
usweis-nr. / 2 ktenzeichen / File ref. letzte Änderung / updated Datum / Date Dieses Blatt gilt nur in Verbindung mit Blatt 1 des sausweises Nr.. Leitungsschutzschalter Circuit-breaker Serie/series 5SL4...-.
MehrPrüfung von Rotorblättern für Windkraftanlagen
Prüfung von Rotorblättern für Windkraftanlagen Florian Sayer www.iwes.fraunhofer.de Kompetenzzentrum Rotorblatt Neue Testverfahren Neue Simulationsverfahren Neue Rotorblätter Material- und Technologieentwicklung
MehrUsing TerraSAR-X data for mapping of damages in forests caused by the pine sawfly (Dprion pini) Dr. Klaus MARTIN klaus.martin@slu-web.
Using TerraSAR-X data for mapping of damages in forests caused by the pine sawfly (Dprion pini) Dr. Klaus MARTIN klaus.martin@slu-web.de Damages caused by Diprion pini Endangered Pine Regions in Germany
Mehrl=var Einseitig Die Leuchte Void hat eine Lichtaustrittsfläche
l=var Linear & modular Void ist eine lineare Wandleuchte für T16 Leuchtstofflampen und lineare LED-Bänder. In Abhängigkeit von der Wattage sind vielfältige Längen für Einzelleuchten verfügbar. Diese wiederum
MehrLWL-Systeme. Fiber Bridge FB. Fiber Optic Systems 7/1 7/2 7/3 7/4 7/5. Systembeschreibung. Analog-, Digital- und Schaltsignale, Kunststoff-LWL
LWL-Systeme Optic Systems Bridge FB eks-fb eks-fb eks-fb eks-fb32 Systembeschreibung System Description Analog-, Digital- und Schaltsignale, Kunststoff-LWL Analog-, Digital and Contact-Closure-Signals,
MehrCable Tester NS-468. Safety instructions
Cable Tester NS-468 Safety instructions Do not use the cable tester NS-468 if it is damaged. This device is only for use inside dry and clean rooms. This device must be protected from moisture, splash
MehrKabel in Transport- und Verteilnetzen/ Deutschland im globalen Kontext
Kabel in Transport- und Verteilnetzen/ Deutschland im globalen Kontext Dena- Dialogforum, Berlin, 27.02.2014 Date 1 AGENDA 1. Prysmiangroup 2. Herausforderungen der Energiemärkte 3. Herausforderungen der
MehrVGM. VGM information. HAMBURG SÜD VGM WEB PORTAL - USER GUIDE June 2016
Overview The Hamburg Süd VGM-Portal is an application which enables to submit VGM information directly to Hamburg Süd via our e-portal web page. You can choose to insert VGM information directly, or download
MehrServiceinformation Nr. 02/11
Serviceinformation Nr. 02/11 vom: 06.10.2011 von: BAM 1. Software Navigator und Release Notes Auf unserer Homepage unter www.idm-energie.at/de/navigator-software.html steht ab sofort eine neue Version
MehrServiceinformation Nr. 05/10
Serviceinformation Nr. 05/10 vom: 05.08.2010 von: GRC 1. Strömungswächter für Grundwasseranlagen Ab sofort können anstelle der Seikom Strömungswächter GF Schwebekörper Durchflussmesser mit Reed Kontakt
MehrTomTom WEBFLEET Tachograph
TomTom WEBFLEET Tachograph Installation TG, 17.06.2013 Terms & Conditions Customers can sign-up for WEBFLEET Tachograph Management using the additional services form. Remote download Price: NAT: 9,90.-/EU:
MehrThe Solar Revolution New Ways for Climate Protection with Solar Electricity
www.volker-quaschning.de The Solar Revolution New Ways for Climate Protection with Solar Electricity Hochschule für Technik und Wirtschaft HTW Berlin ECO Summit ECO14 3. June 2014 Berlin Crossroads to
MehrERNEUERBARE ENERGIEN - WIE WEIT IST DIE ENERGIEWENDE?
ERNEUERBARE ENERGIEN - WIE WEIT IST DIE ENERGIEWENDE? Fraunhofer Institute für Solare Energiesysteme Niklas Kreifels 22. September 2014 www.ise.fraunhofer.de Wieviel Strom verbraucht ein Mensch pro Jahr?
MehrDICO Dimension Coupling
DICO Dimension Coupling 3D!" 1D and phase transition (liquid vapor) Jonathan Jung, Martina Friedrich, Claus-Dieter Munz, Jean-Marc Hérard, Philippe Helluy MAC days, Paris University of Stuttgart Institut
MehrZubehör Accessories Accessoires
Seite Page Page 14/2 DA 14/4 Allgemeine Merkmale Drehantrieb General parameters Rotary drive unit Caractéristiques générales Servomoteur rotatif + 16 Zubehör Accessories Accessoires 14/0 Drehantrieb Rotary
MehrEinsatz einer Dokumentenverwaltungslösung zur Optimierung der unternehmensübergreifenden Kommunikation
Einsatz einer Dokumentenverwaltungslösung zur Optimierung der unternehmensübergreifenden Kommunikation Eine Betrachtung im Kontext der Ausgliederung von Chrysler Daniel Rheinbay Abstract Betriebliche Informationssysteme
MehrInduktive Näherungsschalter inductive proximity switches
Zylindrisch DC cylindric DC Zylindrisch DC Vollmetall cylindric DC full metal Hochtemperatur high temperature Schweißfest weld resistant Druckfest pressure resistant Analog analog Namur namur AC AC Kunststoff
MehrKopenhagen, Dipl.-Ing. Reinhold Weiser Geschäftsführender Gesellschafter / Managing Partner
Kopenhagen, 08.11.2011 Thema/issue: Solarthermie Dipl.-Ing. Reinhold Weiser Geschäftsführender Gesellschafter / Managing Partner AkoTec Produktionsgesellschaft mbh AkoTec Produktionsgesellschaft mbh started
MehrKOMPETENZBROSCHÜRE Competence brochure
KOMPETENZBROSCHÜRE Competence brochure We switch the power! Hauptschalter Not-Aus-Schalter S-Reihe mit Unterspannungsauslösung Main switches Emergency-off switches S series with undervoltage release Schalter
MehrKontaktfärbepapiere Verarbeitungshinweise
Kontaktfärbepapiere Verarbeitungshinweise Transfer Papers Anwendungsbeispiel Example of Use www.teufel-international.com Processing Instructions D Kontaktfärbepapiere Verarbeitungshinweise Kontaktfärbepapiere
MehrGS HYBRID SOLAR INVERTER / / AC-
www.geoprotek.com GS HYBRID SOLAR INVERTER Feed von Solar-und Batteriebetrieb, Grid-Backup, Built-in Transfer Switch / Solar Ladegerät / AC- Ladegerät, 500W ~ 3kW, reine Sinuswelle GS HYBRID ist die ideale
MehrCalibration Services Application Note AN001
The Rosenberger calibration laboratory offers two types of calibration services, the and the. Each calibration kit, calibration standard, gauge and torque wrench comes with a calibration certificate if
MehrCar Adapter photolab 6xxx
Bedienungsanleitung Mit dem können Sie die Spektralphotometer und mobil und unabhängig von der örtlichen Stromversorgung betreiben. Dafür benötigen Sie eine 12 V - Spannungungsversorgung wie z. B. eine
MehrOperation Guide AFB 60. Zeiss - Str. 1 D-78083 Dauchingen
Operation Guide AFB 60 Zeiss - Str. 1 D-78083 Dauchingen PCB automation systems AFB 30/60/90 Die flexiblen Puffer der Baureihe AFB werden zwischen zwei Produktionslinien eingesetzt, um unterschiedliche
MehrAuswertungsbericht Lehrveranstaltungsevaluation an die Lehrenden
Europa-Universität Viadrina Große Scharrnstraße 9 0 Frankfurt (Oder) Europa-Universität Viadrina - Große Scharrnstraße 9-0 Frankfurt (Oder) Sehr geehrter Herr Prof. Dr. Timm Beichelt (PERSÖNLICH) Auswertungsbericht
MehrSupport Technologies based on Bi-Modal Network Analysis. H. Ulrich Hoppe. Virtuelles Arbeiten und Lernen in projektartigen Netzwerken
Support Technologies based on Bi-Modal Network Analysis H. Agenda 1. Network analysis short introduction 2. Supporting the development of virtual organizations 3. Supporting the development of compentences
MehrContext-adaptation based on Ontologies and Spreading Activation
-1- Context-adaptation based on Ontologies and Spreading Activation ABIS 2007, Halle, 24.09.07 {hussein,westheide,ziegler}@interactivesystems.info -2- Context Adaptation in Spreadr Pubs near my location
MehrCameraserver mini. commissioning. Ihre Vision ist unsere Aufgabe
Cameraserver mini commissioning Page 1 Cameraserver - commissioning Contents 1. Plug IN... 3 2. Turn ON... 3 3. Network configuration... 4 4. Client-Installation... 6 4.1 Desktop Client... 6 4.2 Silverlight
MehrThermaltake SMART M650W Bronze
P/N: SP-650M W/Active PFC Thermaltake SMART M650W Bronze Features Entspricht Intel ATX 12V 2.3 & EPS 12V 2.92Standard 24/7 @40 C: garantiert 650 Watt konstante Leistung. Robuste & dedizierte duale +12V
MehrAS Path-Prepending in the Internet And Its Impact on Routing Decisions
(SEP) Its Impact on Routing Decisions Zhi Qi ytqz@mytum.de Advisor: Wolfgang Mühlbauer Lehrstuhl für Netzwerkarchitekturen Background Motivation BGP -> core routing protocol BGP relies on policy routing
MehrFluid-Particle Multiphase Flow Simulations for the Study of Sand Infiltration into Immobile Gravel-Beds
3rd JUQUEEN Porting and Tuning Workshop Jülich, 2-4 February 2015 Fluid-Particle Multiphase Flow Simulations for the Study of Sand Infiltration into Immobile Gravel-Beds Tobias Schruff, Roy M. Frings,
MehrProduktdatenblatt. Artikel Nr.: Wandaufbauleuchte, Alpha II, Weiß, V AC/50-60Hz, 100,00 W. Technische Daten.
Produktdatenblatt Artikel Nr.: 341107 Wandaufbauleuchte, Alpha II, Weiß, 220-240V AC/50-60Hz, 100,00 W Technische Daten Charakteristik Material Farbe Weiß Optik im Lieferumfang Elektrische Daten Leistung
MehrFundamentals of Electrical Engineering 1 Grundlagen der Elektrotechnik 1
Fundamentals of Electrical Engineering 1 Grundlagen der Elektrotechnik 1 Chapter: Operational Amplifiers / Operationsverstärker Michael E. Auer Source of figures: Alexander/Sadiku: Fundamentals of Electric
MehrCurrent distribution effects in a 2.6 ka 2G-Roebel bar
Current distribution effects in a 2.6 ka 2G-Roebel bar University of Houston 4th.-6th. Dec. 2008 W. Goldacker, A. Frank, A.Kudymow, R. Heller, S. Terzieva, A. Kling, C. Schmidt Forschungszentrum Karlsruhe,
MehrLevel of service estimation at traffic signals based on innovative traffic data services and collection techniques
Level of service estimation at traffic signals based on innovative traffic data services and collection techniques Authors: Steffen Axer, Jannis Rohde, Bernhard Friedrich Network-wide LOS estimation at
MehrPNEUMATISCHE PUMPEN PNEUMATIC PUMPS
BVBA POMAC-LUB-SERVICES SPRL Korte Bruggestraat 28 B-8970 Poperinge Tel. 057/33 48 36 Fax 057/33 61 27 info@pomac.be internet: www.pomac.be EINLEITUNGSSCHMIERSYSTEM MIT VOLUMETRISCHEN DOSIERVENTILEN FÜR
MehrProduktinformation 201407_182PNdeen
Produktinformation 201407_182PNdeen Deutsch Seite 1-2 English page 3 4 Produkt Information POWER LIFT HL 2.35 NT DT Fahrzeuge und Transporter werden immer schwerer, von der Automobilindustrie und den Autohäusern
MehrAKTIVE DVB-T ZIMMERANTENNE ANSCHLUSSHINWEISE ACTIVE DVB-T INDOOR ANTENNA CONNECTION INSTRUCTIONS
K la vi er l ac ko p tik AKTIVE DVB-T ZIMMERANTENNE ANSCHLUSSHINWEISE ACTIVE DVB-T INDOOR ANTENNA CONNECTION INSTRUCTIONS ZA 8970 DRUCKS0682.indd 1 05.09.12 15:15 VerpAckunGsinhAlT UKW / UHF / VHF Flachantenne
MehrDialogue: Herr Kruse talks to Herr Meyer about his regular trips to Berlin: Das geht sehr schnell! Es dauert nur etwa 3 Stunden.
Dialogue: Herr Kruse talks to Herr Meyer about his regular trips to Berlin: H.M: H.K: H.M: H.K: H.M: H.K: Fahren Sie regelmäßig nach Berlin? Oh ja, circa 2 bis 3 Mal im Monat. Und wie fahren Sie? Ich nehme
MehrVDE Prüf- und Zertifizierungsinstitut Zeichengenehmigung
Blatt / Page 2 Dieses Blatt gilt nur in Verbindung mit Blatt 1 des sausweises Nr.. This supplement is only valid in conjunction with page 1 of the. PV-Wechselrichter mit selbsttätiger Freischaltstelle
MehrOperation of meshed high voltage direct current (HVDC) overlay grids From operational planning to real time operation
Anne-Katrin Marten Operation of meshed high voltage direct current (HVDC) overlay grids From operational planning to real time operation Universitätsverlag Ilmenau 2015 Impressum Bibliografische Information
MehrFMC. 52 Rosenberger Hochfrequenztechnik GmbH & Co. KG, Germany, Phone +49 (0)8684 18-0, info@rosenberger.de, www.rosenberger.com
The extremely small FMC connector series Flexible Microstrip Connectors are designed for PCB applications in the tightest spaces. Using bullets, equalization of radial and axial misalignments in board-to-board
MehrTitelbild1 ANSYS. Customer Portal LogIn
Titelbild1 ANSYS Customer Portal LogIn 1 Neuanmeldung Neuanmeldung: Bitte Not yet a member anklicken Adressen-Check Adressdaten eintragen Customer No. ist hier bereits erforderlich HERE - Button Hier nochmal
MehrFirefighting System on Container Vessels
Firefighting System on Container Vessels Uwe-Peter Schieder Cargo fires Development of firefighting systems Analogy with fires in buildings Examples Firefighting options today Firefighting options tomorrow
MehrKurzanleitung um Transponder mit einem scemtec TT Reader und der Software UniDemo zu lesen
Kurzanleitung um Transponder mit einem scemtec TT Reader und der Software UniDemo zu lesen QuickStart Guide to read a transponder with a scemtec TT reader and software UniDemo Voraussetzung: - PC mit der
MehrLeistungshalbleiter Bauelemente
Lehrveranstaltung Leistungselektronik Grundlagen und Standard-Anwendungen Leistungshalbleiter Bauelemente Prof. Dr. Ing. Ralph Kennel (ralph.kennel@tum.de) Technische Universität München Arcisstraße 21
MehrInhalt. Trends der Windkraft Entwicklung der Offshore-Windenergienutzung. Technische Entwicklung Zukünftige Aufgaben
Trends der Windkraft Entwicklung der Offshore-Windenergienutzung G.Gerdes Deutsche WindGuard GmbH Dr. Knud Rehfeldt Stiftung OFFSHORE-WINDENERGIE 1 Inhalt Stiftung OFFSHORE-WINDENERGIE Marktentwicklung
MehrSupercomputer für die. Forschungsanlage FAIR. Volker Lindenstruth FIAS, IfI, LOEWE Professur Chair of HPC Architecture
Effizientes Hochleistungsrechnen mit dem GreenCube Supercomputer für die Volker Lindenstruth FIAS, IfI, LOEWE Professur Chair of HPC Architecture Forschungsanlage FAIR University Frankfurt, Germany Phone:
MehrPLUG & PLAY PERFORMANCE TUNING
PLUG & PLAY PERFORMANCE TUNING Die Elektronik des REMUS Powerizers verbessert in Echtzeit die Motorsteuerung. Sie optimiert die Kennfelder mehrmals pro Sekunde und sorgt dadurch für eine deutliche Steigerung
MehrNEWSLETTER. FileDirector Version 2.5 Novelties. Filing system designer. Filing system in WinClient
Filing system designer FileDirector Version 2.5 Novelties FileDirector offers an easy way to design the filing system in WinClient. The filing system provides an Explorer-like structure in WinClient. The
Mehr