Unique Features of Metal Encapsulated SF 6. - Insulated Surge Arresters DANIJEL UDOVCIC

Größe: px
Ab Seite anzeigen:

Download "Unique Features of Metal Encapsulated SF 6. - Insulated Surge Arresters DANIJEL UDOVCIC"

Transkript

1 Unique Features of Metal Encapsulated SF 6 - Insulated Surge Arresters DANIJEL UDOVCIC

2 Unique Features of Metal Encapsulated SF6-Insulated Surge Arresters Siemens AG, Germany D. Udovcic, R. Göhler siemens.com/energy/arrester

3 Overview Arresters Basics 3-10 Traditional Design Improved Design Type tests Overview Conclusion Seite

4 Magnitude of (over.)voltage / p.u. Fundamentals of Insulation Coordination Possible voltages without arresters Withstand voltage of equipment 2 1 Voltages limited by arresters 0 Lightning overvoltages (Microseconds) Switching overvoltages (Milliseconds) Temporary overvoltages (Seconds) Highest system voltage (Continuously) Seite Time duration of (over-)voltage

5 Factor 2.5 MO Arrester: Voltage-Current-Characteristic 1000 Example: U s = 420 kv, Surge arrester U r = 336kV 20-kA residual voltage = lightning impulse protective level = 850 kv 800 Peak value of voltage / kv Peak value rated voltage: 2 Ur= 475 kv Reference voltage: 490 kv Peak value of COV: 2 Uc = 379 kv Peak value of phase-to-earth voltage: 2 Us / 3 = 343 kv Reference current = 5 ma 0 Leakage current 110 µa 0, ,0001 0,001 0,01 0, Peak value of current / A Seite Nominal discharge current = 20 ka 8 orders of magnitude

6 2,5 m Inductivity of current path 1 µh/m (here: L = 10 µh 3,5 m Protective Zone Voltage at terminals of equipment to be protected higher than protection level of arrester Recommendation: Protection level BIL/1,4 Seite

7 Protective Zone Due to travelling wave effects on the line the protection of the equipment by an arrester can be guaranteed only for short distances between arrester and equipment. Simplified estimation of the protective zone *) : xs protective zone in m BIL basic insulation level in kv Upl protection level of the arrester in kv (BIL / 1.15) - Upl s front steepness of the overvoltage in kv/µs xs = v tw (in the range of 1000 kv/µs) 2 s v tw propagation speed of travelling wave: m/µs (overhead line) (equals "c") m/µs (cable) *) For more detailed information see IEC , IEC and IEC Example : Transmission network, Us = 420 kv, effectively earthed, arrester of Ur = 336 kv: xs = (1425 / 1.15) m = 55.5 m Seite

8 2,5 m 3,5 m Increase of Protection Voltage by Inductive Voltage Drops Example: outdoor arrester U s = 420 kv U r = 336 kv u 20kA, 8/20 µs = 850 kv u 20kA, 1/2 µs = 921 kv Surge current path: Specific inductance 1 µh/m / Length 10 m Inductance L 10 µh u= L di / dt residual voltage 1113 kv 921 kv U / kv I / ka 200 current inductive voltage drop t / µs Additional inductive voltage drop kv Seite

9 Increase of Protection Voltage by Inductive Voltage Drops GIS - Arrester U s = 420kV U r = 336 kv u 20kA, 8/20 µs = 840 kv u 20kA, 1/2 µs = 890 kv Surge current path: Specific inductance 0,3 µh/m / Length 2,5 m Inductance L 0,75 µh u= L di / dt Seite Additional inductive voltage drop 10 kv

10 Advantages of Metal Encapsulated SF 6 -Insulated Surge Arresters Optimum protection for GIS and Transformers. Low protection levels that are especially based on the closeness to the equipment that needs to be protected from overvoltages. Best possible protection against the overvoltages, especially those resulting from steep front impulses due to the lower specific inductance. Seite

11 Application area of SF 6 -Insulated Surge Arresters 145kV 3- phase GIS Arrester with SF 6 -SF 6 bushing 420kV Transformer With Oil-SF 6 Bushing Metal Encapsulated SF 6 -Insulated Surge Arrester for 145kV GIS Seite Metal Encapsulated SF 6 -Insulated Surge Arresters for Transformer protection / 420kV

12 Overview Arresters Basics 3-10 Traditional Design Improved Design Type tests Overview Conclusion Seite

13 Traditional Design of SF 6 -Insulated Surge Arresters 3-phase up to U s = 170kV 1-phase up to U s = 420kV Disadvantages: High voltage tests of the GIS at site: Open up of manhole of the arrester. Gas work required. Dimensions: width, length. Layer of the conductor for the three phase arresters has to be announced in advance. More complicated assembly through the part diversity Accessories kit required at site. Seite

14 Overview Arresters Basics 3-10 Traditional Design Improved Design Type tests Overview Conclusion Seite

15 IMPROVED DESIGN OF SF 6 -INSULATED SURGE ARRESTERS 3 Phase Arresters up to 170kV 1 Phase Arresters up to 420 kv Advantages: Disconnector in the series not required anymore. SF 6 -Volume is reduced up to 60%. Plug and Play solution. Reduced gas work at site. Accessories kit not required. Variable phase position at three phase arrester solution. Monitoring or Remote Control of switching position of arresters. Reducing Diversity of the assembled parts Seite

16 Explanation of contacting Upgraded Design Visual switch position indicator: Switch position On, Closed, I Movement of the contact is limited through the external gear. Because of this limitation it is not possible to overwind or to destroy inner contact or inner parts. Visual switch position indicator: Switch position OFF, Open, 0 Legend: 1. SF6-SF6 bushing 2. Active part 3. Insulating rod 4. SF6- Maintenance flange 5. Pressure relief device 6. Terminal for electrical monitoring devices 7. Integrated isolating device 8. Manual drive mechanism Seite

17 Overview Arresters Basics 3-10 Traditional Design Improved Design Type tests Overview Conclusion Seite

18 TYPE TESTS OVERVIEW Vibration broadcom random, class 2M3 acc. IEC Mechanical endurance tests with 1000 switching operations Insulation withstand tests Shock (half sine), class 2M3 acc. IEC Verification of thermal equivalency Internal partial discharge test Seite

19 Overview Arresters Basics 3-10 Traditional Design Improved Design Type tests Overview Conclusion Seite

20 Conclusion Upgraded design setting a new standard through integrated technology based on decades of experience Upgraded design vs. Traditional Design CHARACTERISTICS Upgraded design Traditional design Electrical / Dielectrical behavior same Mechanical behavior same Housing Without manhole With manhole SF6-SF6 bushing Bottom cover Integrated isolating device Manual / Motorized drive mechanism without opening the arrester. same similar Manually disconnection over the manhole. Manual drive mechanism Based on existing one used in traditional design (single-phase up to 245kV) and Trench CTs and VTs. Motorized drive mechanism MOVs (Metal Oxide blocs) DILO / O-rings Rupture disc assembly Based on existing one used in Trench CTs and VTs. same same same No Seite

21 Contact Danijel Udovcic Project manager GIS Arresters Upgraded Design E T HP AR BA P Nonnendammallee Berlin danijel.udovcic@siemens.com siemens.com/answers Seite

ZnO-Arresters for Overvoltage Protection in Pulsed Power Circuits

ZnO-Arresters for Overvoltage Protection in Pulsed Power Circuits European Electromagnetic Launch Society 12th Topical Meeting 10th to 12th September 2001, Ayr ZnO-Arresters for Overvoltage Protection in Pulsed Power Circuits Ulrich Braunsberger Institut für Hochspannungstechnik

Mehr

HH-Sicherungseinsätze mit Steckverbindern für Freileitungsmontage HV fuse links with plug-connectors for overheadline fitting

HH-Sicherungseinsätze mit Steckverbindern für Freileitungsmontage HV fuse links with plug-connectors for overheadline fitting G- HV fuse links with plug-connectors for overheadline fitting HH1-70 HV fuse links including connectors for overhead line fitting Hochspannungs-Sicherungen mit Anschlussgarnitur bilden einen Set, der

Mehr

Snap-in switch for switches PSE, MSM and MCS 30

Snap-in switch for switches PSE, MSM and MCS 30 Product manual Snap-in switch for switches PSE, MSM and MCS 30 CONTENTS 1. PRODUCT DESCRIPTION 2. DATA AND DIMENSIONAL DRAWINGS 2.1. Technical Data 2.2. Dimensions of PSE with a Mounting Diameter 19 mm

Mehr

Datenblatt. P-series PDU 2.5/4/4AN

Datenblatt. P-series PDU 2.5/4/4AN Turn five into three that's the winning formula of the new P series with the PUSH IN connection system in which the pitches for 2.5, 4, 6 and 10 mm² are each combined in one terminal block. That means

Mehr

Electrical tests on Bosch unit injectors

Electrical tests on Bosch unit injectors Valid for Bosch unit injectors with order numbers 0 414 700 / 0 414 701 / 0 414 702 Parts Kit Magnet*: - F00H.N37.925 - F00H.N37.933 - F00H.N37.934 * For allocation to the 10-place Bosch order number,

Mehr

Hazards and measures against hazards by implementation of safe pneumatic circuits

Hazards and measures against hazards by implementation of safe pneumatic circuits Application of EN ISO 13849-1 in electro-pneumatic control systems Hazards and measures against hazards by implementation of safe pneumatic circuits These examples of switching circuits are offered free

Mehr

MINI 1-Conductor/1-Pin Receptacle Terminal Blocks; 2-Conductor/2-Pin Receptacle Terminal Blocks, Series 2020

MINI 1-Conductor/1-Pin Receptacle Terminal Blocks; 2-Conductor/2-Pin Receptacle Terminal Blocks, Series 2020 X-COM @-SYSTEM MINI 1-Conductor/1-Pin Receptacle Terminal Blocks; 2-Conductor/2-Pin Receptacle Terminal Blocks, Series 2020 0.14 1 (1.5) mm 2 AWG 24 16 500 V/6 kv/3 1 13.5 A* 0.14 1 (1.5) mm 2 AWG 24 16

Mehr

Overview thermostat/ temperature controller

Overview thermostat/ temperature controller Thermostat TR-238 The Thermostat TR-238 is a electronic two-level controller for controlling of and in climate control units and vehicles. Voltage range (12V): Voltage range (24V): Control range: Hystereses:

Mehr

19 Network Cabinet Modular, Unequipped Frame for modular upgrading or use as open rack

19 Network Cabinet Modular, Unequipped Frame for modular upgrading or use as open rack 19 Network Cabinet Modular, Unequipped Frame for modular upgrading or use as open rack page 1 of 6 Art.-No. 692515U.. 692447U unequipped basic frame for modular upgrading depth-adjustable 19 profiles with

Mehr

Electrical testing of Bosch common rail piezo injectors

Electrical testing of Bosch common rail piezo injectors Applies to generation CRI 3: Bosch 10-position order number 0 445 115 = CRI 3-16 (CRI 3.0) 1600 bar 0 445 116 = CRI 3-18 (CRI 3.2) 1800 bar 0 445 117 = CRI 3-20 (CRI 3.3) 2000 bar Tools required: Hybrid

Mehr

With your design proposals or our available simulation and calculation programs, our R&D department realizes and delivers quick solutions.

With your design proposals or our available simulation and calculation programs, our R&D department realizes and delivers quick solutions. HAHN offers solutions for product developers of switching power supplies. In response to the variety of designs which are available on the market, HAHN combines demands and wishes of the developers to

Mehr

ORION three-phase 2-250kVA

ORION three-phase 2-250kVA ORION three-phase 2-250kVA Orion stabilizers are available for different ranges of input voltage fluctuation. Standard models offer a double input connection so that with the same unit two different input

Mehr

Electrical testing of Bosch common rail solenoid valve (MV) injectors

Electrical testing of Bosch common rail solenoid valve (MV) injectors Applies to MV injector, generation: -CRI 1.0 / 2.0 / 2.1 / 2.2 -CRIN 1 / 2 / 3, with K oder AK plug Bosch 10-position order number Bosch-Bestellnummer CRI: 0 445 110 xxx Bosch-Bestellnummer CRIN: 0 445

Mehr

HH 2. HH-Sicherungen HV fuse-links. Strombegrenzung. Current limitation

HH 2. HH-Sicherungen HV fuse-links. Strombegrenzung. Current limitation 6 Strombegrenzung Bei hohen Kurzschlussströmen unterbrechen die den Strom innerhalb weniger Millisekunden. Das heißt, dass der sinusförmige Strom seinen Scheitelwert nicht erreicht, die somit strombegrenzend

Mehr

Shock pulse measurement principle

Shock pulse measurement principle Shock pulse measurement principle a [m/s²] 4.0 3.5 3.0 Roller bearing signals in 36 khz range Natural sensor frequency = 36 khz 2.5 2.0 1.5 1.0 0.5 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0 350 360 370 380 390

Mehr

Datenblatt. Remote-I/O - u-remote UR20-4AO-UI or 4-wire connection; 16-bit resolution; 4 outputs

Datenblatt. Remote-I/O - u-remote UR20-4AO-UI or 4-wire connection; 16-bit resolution; 4 outputs 2- or 4-wire connection; 16-bit resolution; 4 outputs The analogue output module controls up to 4 analogue actuators with +/-10 V, +/-5 V, 0...10 V, 0...5 V, 2...10 V, 1...5 V, 0...20 ma or 4...20 ma with

Mehr

16.7 Hz - The Missing Link?

16.7 Hz - The Missing Link? 16.7 Hz - The Missing Link? Prof. István Erlich University of Duisburg-Essen Bremen, January 2014 Current Concept 2 Current Concept Offshore Onshore WP1 33 kv AC, 50 Hz WP-Plattform WP-Plattform 150 kv

Mehr

H o c h s c h u l e D e g g e n d o r f H o c h s c h u l e f ü r a n g e w a n d t e W i s s e n s c h a f t e n

H o c h s c h u l e D e g g e n d o r f H o c h s c h u l e f ü r a n g e w a n d t e W i s s e n s c h a f t e n Time Aware Shaper Christian Boiger christian.boiger@hdu-deggendorf.de IEEE 802 Plenary September 2012 Santa Cruz, California D E G G E N D O R F U N I V E R S I T Y O F A P P L I E D S C I E N C E S Time

Mehr

Newest Generation of the BS2 Corrosion/Warning and Measurement System

Newest Generation of the BS2 Corrosion/Warning and Measurement System Newest Generation of the BS2 Corrosion/Warning and Measurement System BS2 System Description: BS2 CorroDec 2G is a cable and energyless system module range for detecting corrosion, humidity and prevailing

Mehr

Quadt Kunststoffapparatebau GmbH

Quadt Kunststoffapparatebau GmbH Quadt Kunststoffapparatebau GmbH Industriestraße 4-6 D-53842 Troisdorf/Germany Tel.: +49(0)2241-95125-0 Fax.: +49(0)2241-95125-17 email: info@quadt-kunststoff.de Web: www.quadt-kunststoff.de Page 1 1.

Mehr

Electrical testing of Bosch common rail Injectors

Electrical testing of Bosch common rail Injectors Electrical testing of Bosch common rail Injectors Contents: 1. Adapter cable for Hybridtester FSA 050 (article number 0 684 010 050 / 1 687 023 571) 2. Electrical testing of Bosch common rail solenoid

Mehr

Power supply Interference suppressed acc. to DIN EN /- 4, EN 55011, EN CI. B, power factor corrected Power factor BöSha LED driver

Power supply Interference suppressed acc. to DIN EN /- 4, EN 55011, EN CI. B, power factor corrected Power factor BöSha LED driver Operating Instructions LED Mast Double Luminaire Callisto SC DB, incl. Inclination Adjustment, Single-Chip Technology (Please, read carefully before starting operation) Version: 16.01.2017 Model 369-M

Mehr

Control shut-off butterfly valves DN 50 DN 400 PN

Control shut-off butterfly valves DN 50 DN 400 PN Features Applications include HEVAC and drinking water systems, sanitary and industrial plants for control or shut-off of water and steam -10...+110 C Leakage rate: tight sealing Control and shut-off butterfly

Mehr

Controlled Switching suitability check for already installed HVAC circuit breakers

Controlled Switching suitability check for already installed HVAC circuit breakers Controlled Switching suitability check for already installed HVAC circuit breakers Dipl. El.-Ing. Urs Krüsi Swiss Federal Institute of Technology, Zurich, CH STRUCTURE INTRODUCTION IMPORTANT CHARACTERISTICS

Mehr

Umschaltventile Magnete

Umschaltventile Magnete Umschaltventile Magnete DFE1/6 estellnr. Typ 2-11-12 DFE1/618ES-W22-12VDC 2-11-13 DFE1/618ES-W22-24VDC 24--116 DFE1/618ES-Y22-12VDC 24--117 DFE1/618ES-Y22-24VDC 24--1 DFE1/618ES-W22-12VDC 24--12 DFE1/618ES-W22-24VDC

Mehr

ABB i-bus EIB. EIB Power Supply Units

ABB i-bus EIB. EIB Power Supply Units ABB i-bus EIB EIB Power Supply Units Product Range Overview EIB Power Supplies ABB STOTZ-KONTAKT GmbH, 2002 - SK 029 F 02 E Product Range Overview EIB Power Supplies! EIB Power Supply, 320 ma SV/S 30.320.5!

Mehr

PI-T001/c. Developed especially for short-circuit protection in Telekom DC-power supply requirements.

PI-T001/c. Developed especially for short-circuit protection in Telekom DC-power supply requirements. NH-Sicherungslasttrennschalter und NH-Sicherungen für die Stromversorgung von Telekommunikationseinrichtungen LV HRC fuse switch-disconnectors and LV HRC fuses for telecom power supply Speziell für den

Mehr

splicetec ag Boesch 37 CH-6331 Huenenberg Tel +41 (0) Fax +41 (0)

splicetec ag Boesch 37 CH-6331 Huenenberg Tel +41 (0) Fax +41 (0) Erdungsboxen für Crossbonding und Schirmtrennung Anwendung Starre Erdung Erdung mit Überspannungsableitern Auskreuzung Leistungsmerkmale Kompakte Bauweise Edelstahl Hermetisch abgedichtet 1-Phasen- und

Mehr

Asynchronous Generators

Asynchronous Generators Asynchronous Generators Source: ABB 1/21 2. Asynchronous Generators 1. Induction generator with squirrel cage rotor 2. Induction generator with woed rotor Source: electricaleasy.com 2/21 2.1. Induction

Mehr

Umschaltventile Magnet

Umschaltventile Magnet Umschaltventile Magnet DFE1/3 estellnr. Typ 2-11-1 DFE1/318ES-W22-12VDC 2-11-1 DFE1/318ES-W22-24VDC 24-2-116 DFE1/318ES-Y22-12VDC 24-2-117 DFE1/318ES-Y22-24VDC Weitere Umschaltventil Varianten auf nfrage

Mehr

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Anlage zur Akkreditierungsurkunde D-PL-11055-09-00 nach DIN EN ISO/IEC 17025:2005 Gültigkeitsdauer: 09.02.27 bis 18.10.2020 Ausstellungsdatum: 09.02.27 Urkundeninhaber:

Mehr

Machine Brochure. MÜLLER WEINGARTEN Blanking line. https://youtu.be/1_gz2wxmmo

Machine Brochure. MÜLLER WEINGARTEN Blanking line. https://youtu.be/1_gz2wxmmo Machine Brochure MÜLLER WEINGARTEN Blanking line https://youtu.be/1_gz2wxmmo0 7-40263 Goedicke Werkzeugmaschinenhandels GmbH Heinz-Nixdorf-Straße 2 74172 Neckarsulm GERMANY +49 (0) 7132 99936 0 www.goedicke.com

Mehr

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH nach DIN EN ISO/IEC 17025:2005 Gültigkeitsdauer: 09.02.2017 bis 18.10.2020 Ausstellungsdatum: 09.02.2017 Urkundeninhaber: PEHLA - Gesellschaft für elektrische Hochleistungsprüfungen

Mehr

Deceleration Technology. Rotary Dampers with high-torque range WRD-H 0607 WRD-H 0805 WRD-H 1208 WRD-H 1610 WRD-H

Deceleration Technology. Rotary Dampers with high-torque range WRD-H 0607 WRD-H 0805 WRD-H 1208 WRD-H 1610 WRD-H Rotary Dampers with high-torque range WRD-H 67 WRD-H 85 WRD-H 128 WRD-H 161 WRD-H 21 Deceleration Technology ONLINE CALCULATION AND 2D / 3D CAD DOWNLOAD M m L F Benefits Applications: - Mechanical and

Mehr

Dreiphasen-Stromwandlersätze Three-phase current transformer sets

Dreiphasen-Stromwandlersätze Three-phase current transformer sets MBS SULZBACH MESSWANDLER GmbH Dreiphasen-wandlersätze Three-phase transformer sets WSKD 31.8 / ASKD 31.8 mit Abdeckkappen aus Plexiglas Ausführung: Die Messwandlersätze der Typenreihe WSKD 31.8 / ASKD

Mehr

Earthing switch Technical Data

Earthing switch Technical Data arthing switch Technical ata eatures and benefits ompact design ll steel parts either in stainless steel or hot-dip galvanised Solid and stable base frame Minimal sag for the line-connection thanks to

Mehr

Fuse bases for DC Sicherungsunterteile und Sicherungs-Lasttrennschalter für Fotovoltaikanwendungen

Fuse bases for DC Sicherungsunterteile und Sicherungs-Lasttrennschalter für Fotovoltaikanwendungen 15 00 V! Fuse bases for DC Sicherungsunterteile und Sicherungs-Lasttrennschalter für Fotovoltaikanwendungen Pronutec offers his Fuse bases for DC installations up to 1500 V: the 1P NH type Fuse bases with

Mehr

Technical Terms Technische Daten: Operating voltage Betriebsspannungsbereich Rated Voltage Nennspannung

Technical Terms Technische Daten: Operating voltage Betriebsspannungsbereich Rated Voltage Nennspannung Technical Terms Technische Daten: Operating voltage Betriebsspannungsbereich Rated Voltage Nennspannung 4...7 V 5 V *) Rated Current Nennstrom < 50 ma Sound Output [SPL]at 10 cm Lautstärke[Schalldruckpegel]

Mehr

Deceleration Technology. Rotary Dampers mit hohem Drehmoment WRD-H 2515 WRD-H 3015 WRD-H 4025 WRD-H

Deceleration Technology. Rotary Dampers mit hohem Drehmoment WRD-H 2515 WRD-H 3015 WRD-H 4025 WRD-H Rotary Dampers mit hohem Drehmoment WRD-H 2515 WRD-H 3015 WRD-H 4025 WRD-H 6030 Deceleration Technology ONLINE CALCULATION AND 2D / 3D CAD DOWNLOAD M m L F Benefits Material: - Aluminium and steel Applications:

Mehr

Deceleration Technology. Rotary Dampers with high-torque range WRD-H 7550 WRD-H 9565 WRD-H

Deceleration Technology. Rotary Dampers with high-torque range WRD-H 7550 WRD-H 9565 WRD-H Rotary Dampers with high-torque range WRD-H 7550 WRD-H 9565 WRD-H 12070 Deceleration Technology ONLINE CALCULATION AND 2D / 3D CAD DOWNLOAD M m L F Benefits Material: - Aluminium and steel Applications:

Mehr

Sicherungsunterteile / fuse base. Mikroschalter / Aux. Switch. Artikel-Nr. Verzeichnis / part-no. index

Sicherungsunterteile / fuse base. Mikroschalter / Aux. Switch. Artikel-Nr. Verzeichnis / part-no. index Auswahltabelle / selection guide Typ type Bemessungsspannung rated voltage Größe size Mikroschalteranbau möglich micro switch fiing provided Abbildung figure Artikel-Nr. part-no. techn. Daten - Seite techn.

Mehr

Datenblatt / Data sheet

Datenblatt / Data sheet Seite/Page 1/5 Abbildungen / Illustration Maßzeichnung / Dimensions Produktbeschreibung Product specification Kompaktes, steckbares Relais für den industriellen Einsatz. Compact, pluggable relay for industrial

Mehr

Typenreihe GH Lifting Solenoids

Typenreihe GH Lifting Solenoids Hubmagnete Lifting Solenoids Bauart Hubmagnete der Reihe GH können mit Durchmessern zwischen 5 mm und 65 mm und mit Hublängen von 8 bis 60 mm gefertigt werden. Serien mäßig wer den sie mit Wellenenden

Mehr

Certificate of conformity Generating unit, NS-protection

Certificate of conformity Generating unit, NS-protection Applicant: Product: Certificate of conformity Generating unit, NS-protection Schneider Electric Solar Inverters USA, Inc. 250 South Vasco Road Livermore, California 94551 USA Photovoltaic Inverter with

Mehr

INCLUDES: Fully assembled 4 wheels for mobile use Power cable

INCLUDES: Fully assembled 4 wheels for mobile use Power cable LN 00-SERIES technical data LN 65 Areas of APPLICATION: Soldering (single/multi-site extraction) Laser processing (source extraction tubes, or large laser cabinets) Processes for working with adhesive/moist

Mehr

tigspeed oscillation drive 45 hotwire

tigspeed oscillation drive 45 hotwire tigspeed oscillation drive 45 hotwire 090-000180-00502 TIG cold wire and hot wire welding with dynamic wire feed system Dynamic wire feeding for a controllable weld pool even with positional welding: The

Mehr

a new line of steam sterilizers

a new line of steam sterilizers a new line of steam sterilizers ticheeasy to use and high consumption savings multifunction display controlled by micro-processor double and patented motor-operated closure stainless steel chamber without

Mehr

C 146 EMV Gehäuse/EMC Housings

C 146 EMV Gehäuse/EMC Housings 146 EMV Gehäuse/EM Housings Für Serien 146 E 6-24 pol 146 D 4-64 pol 146 M 2-7 Module 146 HSE 6 pol For series 146 E 6-24 contacts 146 D 4-64 contacts 146 M 2-7 Module 146 HSE 6 contacts mphenol 151 146

Mehr

Dynamic Hybrid Simulation

Dynamic Hybrid Simulation Dynamic Hybrid Simulation Comparison of different approaches in HEV-modeling GT-SUITE Conference 12. September 2012, Frankfurt/Main Institut für Verbrennungsmotoren und Kraftfahrwesen Universität Stuttgart

Mehr

technical documents for extraction and filter devices type series 1000

technical documents for extraction and filter devices type series 1000 technical documents for extraction and filter devices type series 1000 5. suction flange 6. filter combination 7. fan / motor 8. air outlet Functional principle: A special fan (3) with a high pressure

Mehr

Phase Connecting Elements. Earth. M16: 150 Nm Angled fixed ball point

Phase Connecting Elements. Earth. M16: 150 Nm Angled fixed ball point ing Sticks EaS Fixed Ball Points Ø20 or 25 mm Suitable for fixing cable lugs or connecting busbars in accordance with DIN 43673-1 Self-locking nut M12 or M16 female thread (not cut) M12 or M16 threaded

Mehr

Kabelgarnituren für Mittel- und Hochspannungsnetze Cable fittings for medium and high voltage networks

Kabelgarnituren für Mittel- und Hochspannungsnetze Cable fittings for medium and high voltage networks Kontaktsysteme für Energienetze Contact systems for power networks Kabelgarnituren für ittel- und Hochspannungsnetze Cable fittings for medium and high voltage networks 4.1 CONNEX-Überspannungsableiter

Mehr

Cycling. and / or Trams

Cycling. and / or Trams Cycling and / or Trams Experiences from Bern, Switzerland Roland Pfeiffer, Departement for cycling traffic, City of Bern Seite 1 A few words about Bern Seite 2 A few words about Bern Capital of Switzerland

Mehr

Typenreihe GH Lifting Solenoids

Typenreihe GH Lifting Solenoids Hubmagnete Lifting Solenoids Bauart Hubmagnete der Reihe GH können mit Durchmessern zwischen 5 mm und 65 mm und mit Hublängen von 8 bis 60 mm gefertigt werden. Serien mäßig wer den sie mit Wellenenden

Mehr

Certificate of conformity Generating unit, NS-protection

Certificate of conformity Generating unit, NS-protection Certificate of conformity Generating unit, NS-protection Applicant: Product: Schneider Electric Solar Inverters USA, Inc. 250 South Vasco Road Livermore, California 94551 USA Photovoltaic Inverter with

Mehr

Overcurrent Protection Leaded Disks, Coated, 12 V, 24 V

Overcurrent Protection Leaded Disks, Coated, 12 V, 24 V B99* C 93 C 99 Applications Overcurrent and short-circuit protection b 3, max. Features Lead-free terminals Manufacturer s logo and type designation stamped on in white Low resistance For rated currents

Mehr

Brand Label. Daimler Brand & Design Navigator

Brand Label. Daimler Brand & Design Navigator Daimler Brand & Design Navigator 30. März 2016 Brand Label FUSO Financial uses the FUSO letters in combination with the word Financial in the font Daimler CS for name and label. Black lettering is set

Mehr

Sensors Motor Protection, Triple Sensors

Sensors Motor Protection, Triple Sensors B900 M 00 Applications Thermal protection of winding in electric motors Limit temperature monitoring Features Thermistor pellets with insulating encapsulation in series connection (triple sensor) Low-resistance

Mehr

Datasheet. Page 1 of 7

Datasheet. Page 1 of 7 Features 20 Encoder Positions 4-way Joystick LED-Illumination high quality signal processing Benefits Tactile multi purpose application premium design Hall Effect technology Applications Multiple switch

Mehr

OPERATING INSTRUCTIONS Test pump ZG 5.1. and ZG 5.2.

OPERATING INSTRUCTIONS Test pump ZG 5.1. and ZG 5.2. Elektromotoren und Gerätebau Barleben GmbH OPERATING INSTRUCTIONS Test pump ZG 5.1. and ZG 5.2. Elektromotoren und Gerätebau Barleben GmbH 2 Inhaltsverzeichnis Page 1 Use 4 2 Design features 4 2.1 Test

Mehr

Oil / Air cooler ASA-TT 11 12V/24V DC Öl /Luftkühler ASA-TT 11 12V/24V DC

Oil / Air cooler ASA-TT 11 12V/24V DC Öl /Luftkühler ASA-TT 11 12V/24V DC Oil / Air cooler ASATT 11 12V/24V DC Öl /Luftkühler ASATT 11 12V/24V DC Pressure drop at 30 cst Druckabfall bei 30 cst Specific Cooling Performance Spezifische Kühlleistung TECHNICAL DATA TECHNISCHE DATEN

Mehr

HVDC and FACTS. Flexible Alternative Current Transmission Systems. Modul in Studiengängen Elektrotechnik und Energiewirtschaft

HVDC and FACTS. Flexible Alternative Current Transmission Systems. Modul in Studiengängen Elektrotechnik und Energiewirtschaft Page No 1 of 16 HVDC and FACTS HVDC FACTS High Voltage Direct Current Flexible Alternative Current Transmission Systems Modul in Studiengängen Elektrotechnik und Energiewirtschaft Zeitraum: SS 2017 Umfang:

Mehr

NH-Sicherungseinsätze der Betriebsklasse gg AC690V mit Kombi-Melder LV HRC fuse-links uzilization class gg AC690V with combi indicator

NH-Sicherungseinsätze der Betriebsklasse gg AC690V mit Kombi-Melder LV HRC fuse-links uzilization class gg AC690V with combi indicator NH-Sicherungseinsätze der Betriebsklasse gg AC690V mit LV HRC fuse-links uzilization class gg AC690V with combi indicator JEAN MÜLLER NH-Sicherungseinsätze der Betriebsklasse gg AC690V sind ab sofort mit

Mehr

S202M-C10. Miniature Circuit Breaker - S200M - 2P - C - 10 ampere. General Information. Ordering. Popular Downloads. Dimensions. Technical S202M-C10

S202M-C10. Miniature Circuit Breaker - S200M - 2P - C - 10 ampere. General Information. Ordering. Popular Downloads. Dimensions. Technical S202M-C10 ABB Miniature Circuit Breaker - S200M - 2P - C - 10 ampere General Information Extended Product Type Product ID S202M-C10 2CDS272001R0104 EAN 4016779550284 Catalog Description Long Description Miniature

Mehr

New ways of induction heating in the injection moulding process

New ways of induction heating in the injection moulding process New ways of induction heating in the injection moulding process Micro Technology innovation forum Villingen-Schwenningen February 29, 2012 Dipl.-Ing. M. Maier Prof. Dr.-Ing. W. Schinköthe Institut für

Mehr

ICL Series Rail-Mount Hydraulic Magnetic Circuit Breaker

ICL Series Rail-Mount Hydraulic Magnetic Circuit Breaker Ihr autorisierter Distributor: Neumüller Elektronik GmbH info@hq-schutzschalter.de ICL Series Rail-Mount Hydraulic Magnetic Circuit Breaker Introduction 133 Configurations 134 Operating Characteristics

Mehr

- Characteristic sensitive Small temperature differences. - Low Sensitivity 42,8 µv/k for Cu-Constantan

- Characteristic sensitive Small temperature differences. - Low Sensitivity 42,8 µv/k for Cu-Constantan Thermocouples + Lightweight Small backlash by deformations + No self heating + Physically defined Zero No calibration for control loops - Characteristic sensitive Small temperature differences to cable

Mehr

Pilot Project Biogas-powered Micro-gas-turbine

Pilot Project Biogas-powered Micro-gas-turbine 1/18 Pilot Project Biogas-powered Micro-gas-turbine Supported by the Hessischen Ministerium für Wirtschaft, Verkehr und Landesentwicklung Speaker Details 2/18 Jan Müller Works at Institute of Solar Energy

Mehr

WICSTYLE 65. Beschläge Fittings. Elektrische Türöffner Electric door opener. Attribut Attribute. Farbe Color. Artikel Article DIN DIN VE PU

WICSTYLE 65. Beschläge Fittings. Elektrische Türöffner Electric door opener. Attribut Attribute. Farbe Color. Artikel Article DIN DIN VE PU e 6920072 mit mech. with mechanical Modell 8 ProFix 2 Ausführung Nennspannung 0-24 Volt AC / DC Wechsel- und Gleichstrom Einschaltdauer bei 2 V DC 00% Bei 0-2 Volt DC zusätzlich verwenden. Model 8 Rated

Mehr

Simulating the Idle: A New Load Case for Vehicle Thermal Management

Simulating the Idle: A New Load Case for Vehicle Thermal Management Simulating the Idle: A New Load Case for Vehicle Thermal Management Jan Eller FKFS / IVK University of Stuttgart Thomas Binner and Heinrich Reister Daimler AG Nils Widdecke and Jochen Wiedemann FKFS /

Mehr

Walter Buchmayr Ges.m.b.H.

Walter Buchmayr Ges.m.b.H. Seite 1/10 Chapter Description Page 1 Advantages 3 2 Performance description 4 3 Settings 5 4 Options 6 5 Technical data 7 6 Pictures 8 http://members.aon.at/buchmayrgmbh e-mail: walter.buchmayr.gmbh@aon.at

Mehr

Motion Controller 2 - MC2

Motion Controller 2 - MC2 otion ler 2 - C2 otion ler C2 The C2 (otion ler) is the connective link between a higher-ranking control level (PLC, IPC etc.) and one or more SIEB & EYER drives (series SD2/SD2S and FC2). It receives

Mehr

prorm Budget Planning promx GmbH Nordring Nuremberg

prorm Budget Planning promx GmbH Nordring Nuremberg prorm Budget Planning Budget Planning Business promx GmbH Nordring 100 909 Nuremberg E-Mail: support@promx.net Content WHAT IS THE prorm BUDGET PLANNING? prorm Budget Planning Overview THE ADVANTAGES OF

Mehr

How-To-Do. Hardware Configuration of the CC03 via SIMATIC Manager from Siemens

How-To-Do. Hardware Configuration of the CC03 via SIMATIC Manager from Siemens How-To-Do Hardware Configuration of the CC03 via SIMATIC Manager from Siemens Content Hardware Configuration of the CC03 via SIMATIC Manager from Siemens... 1 1 General... 2 1.1 Information... 2 1.2 Reference...

Mehr

S201-C6. Miniature Circuit Breaker - S200-1P - C - 6 ampere. General Information. Ordering. Popular Downloads. Dimensions.

S201-C6. Miniature Circuit Breaker - S200-1P - C - 6 ampere. General Information. Ordering. Popular Downloads. Dimensions. ABB Miniature Circuit Breaker - S200-1P - C - 6 ampere General Information Extended Product Type Product ID S201-C6 2CDS251001R0064 EAN 4016779464000 Catalog Description Long Description Miniature Circuit

Mehr

19 Network Cabinet Standard with Rear Door in Full Cabinet Height. depth-adjustable 19 profiles with numbering of rack units

19 Network Cabinet Standard with Rear Door in Full Cabinet Height. depth-adjustable 19 profiles with numbering of rack units depth-adjustable 19 profiles with numbering of rack units rear door in full height with 2-point latch locking Common Specifications 19 network cabinet according to DIN41494 Steel sheet housing with welded

Mehr

We are pleased to inform you that the addendum this requires to the existing product approval has now been successfully completed.

We are pleased to inform you that the addendum this requires to the existing product approval has now been successfully completed. MSA AUER GmbH! Thiemannstraße 1! D-12059 Berlin To our customers Name Phone, Fax E-mail Date Malte Kaas (030) 6886-0, -1613 Malte.Kaas@MSAsafety.com 10.12.2014 Duracell MN 1500 Procell Retail availability

Mehr

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH nach DIN EN ISO/IEC 17025:2005 Gültigkeitsdauer: 26.11.2015 bis 25.11.2020 Ausstellungsdatum: 26.11.2015 Urkundeninhaber: PEHLA - Gesellschaft für elektrische Hochleistungsprüfungen

Mehr

Copyright by Max Weishaupt GmbH, D Schwendi

Copyright by Max Weishaupt GmbH, D Schwendi Improving Energy Efficiency through Burner Retrofit Overview Typical Boiler Plant Cost Factors Biggest Efficiency Losses in a boiler system Radiation Losses Incomplete Combustion Blowdown Stack Losses

Mehr

rear view server cabinet perforated steel door, divided

rear view server cabinet perforated steel door, divided 19 Server Cabinet Standard Page 1 of 5 Art.-No. 693126.60P1P2.. 693147.82P2 depth rail + traverse for high max. load front view server cabinet perforated steel door, one-part rear view server cabinet perforated

Mehr

BNC - Programm BNC Programme

BNC - Programm BNC Programme - Programm S. 215 Adapter Adapters S. 217 -Adapterleitungen adapter leads S. 218 Sicherheits-Adapter Safety adapters www.schuetzinger.de 213 - Programm Die HF-Steckverbindung der Serie ist die häufigste

Mehr

Protection modular systems for DIN rail and 60mm busbar system DIN-Hutschienen-und 60mm Sammelschienenkomponenten

Protection modular systems for DIN rail and 60mm busbar system DIN-Hutschienen-und 60mm Sammelschienenkomponenten Protection modular systems for DIN rail and 60mm busbar system DIN-Hutschienen-und 60mm Sammelschienenkomponenten 2 Contents / Inhaltsverzeichnis Page Seite 1 2 60mm Classic Busbar System / 60mm Classic

Mehr

SIRIUS ADVANCE three-phase kVA

SIRIUS ADVANCE three-phase kVA SIRIUS ADVANCE three-phase 60-4000kVA Sirius Advance voltage stabilizers derive from the SIRIUS type, of which they maintain the main technical characteristics. The standard integration of some functions

Mehr

Stromzwischenkreisumrichter Current Source Inverter (CSI)

Stromzwischenkreisumrichter Current Source Inverter (CSI) course " Power Electronics" Stromzwischenkreisumrichter Current Source Inverter (CSI) Prof. Dr. Ing. Ralph Kennel (ralph.kennel@tum.de) Arcisstraße 21 80333 München Converters converters Stromrichter power

Mehr

Electromagnetic Flowmeter FXE4000-DE43F

Electromagnetic Flowmeter FXE4000-DE43F Pos: 2 /Grid-Layout/Titelblätter/Ersatzteilblätter/Durchfluss/FXE4000-DE43F @ 65\mod_1350460748604_3101.docx @ 523546 @ @ 1 === Ende der Liste für Textmarke Cover === Spare Parts List SPL/FXE4000-DE43F-EN

Mehr

Schalten einer kapazitiven Last mit einem Transistor

Schalten einer kapazitiven Last mit einem Transistor . Schalten einer kapazitiven Last mit einem Transistor In allgemeinen technischen Anwendungen ist das Schalten einer kapazitiven Last eher von untergeordneter Bedeutung. In Rechnersystemen (Computernetzwerken)

Mehr

Zehnder CLD. Housing for walls, floors and ceilings

Zehnder CLD. Housing for walls, floors and ceilings Benefits Suitable for wall, floor or ceiling installation Air volumes up to a maximum of 30 m 2 /h (ComfoTube 75) and 45 m 2 /h (ComfoTube 90) Can be installed in timber or solid constructions Extract

Mehr

high potential insulating transformer Hochpotenzial- Trenntrafo bis 80 kv Potenzialtrennung up to 80 kv potential difference Tauscher Transformatoren

high potential insulating transformer Hochpotenzial- Trenntrafo bis 80 kv Potenzialtrennung up to 80 kv potential difference Tauscher Transformatoren Hochpotenzial - Hochspannungs - Trenntransformatoren pri - sec und einer Leistung von 1 VA bis 3000 VA Isoliertrafo, Isolationstransformator Einsatzmöglichkeiten Hochspannungstrenntransformatoren werden

Mehr

Position switch // ES 95 / EM 95

Position switch // ES 95 / EM 95 Features/Options Thermoplastic enclosure Horizontally slotted mounting holes Double insulated X ES 95: Slow action A, change-over contact, change-over contact with overlapping, 2 NC contacts or 2 NO contacts

Mehr

R&R. Ges. für Rationalisierung und Rechentechnik mbh. R&R RR-P-508 / ST106-EX1 motor-control unit

R&R. Ges. für Rationalisierung und Rechentechnik mbh. R&R RR-P-508 / ST106-EX1 motor-control unit R&R R&R RR-P-08 / ST06-EX motor-control unit housing wxhxd weight application power supply aluminum anodized approx. 6 x 8 x 8 mm housing similar to ST0 drawing DNR967 approx. 80 g motor desk control unit

Mehr

WE SHAPE INDUSTRY 4.0 BOSCH CONNECTED INDUSTRY DR.-ING. STEFAN AßMANN

WE SHAPE INDUSTRY 4.0 BOSCH CONNECTED INDUSTRY DR.-ING. STEFAN AßMANN WE SHAPE INDUSTRY 4.0 BOSCH CONNECTED INDUSTRY DR.-ING. STEFAN AßMANN Bosch-Definition for Industry 4.0 Our Seven Features Connected Manufacturing Connected Logistics Connected Autonomous and Collaborative

Mehr

P A max. 100bar A P max. 16bar

P A max. 100bar A P max. 16bar 1 Schaltfunktion A: function A: direktgesteuert Modulbauweise NC (stromlos geschlossen) Schaltfunktion B: NC (normally closed) function B: NO (stromlos offen) NO (normally open) direct acting modular design

Mehr

Anwendungsbeispiele FW 50 +.SI / FW 60 +.SI Examples for FW 50 +.SI / FW 60 +.SI

Anwendungsbeispiele FW 50 +.SI / FW 60 +.SI Examples for FW 50 +.SI / FW 60 +.SI Schüco 21 Anwendungsbeispiele FW +.SI / FW 60 +.SI Examples for FW +.SI / FW 60 +.SI Die hier gezeigten Elementsymbole geben eine Übersicht der möglichen Bauformen. Alle auf dieser Seite angegebenen Zahlen

Mehr

PROFIBUS-DP Repeater 1 to 1 and 1 to 5 with optional level converter module

PROFIBUS-DP Repeater 1 to 1 and 1 to 5 with optional level converter module LSS PROFIBUS-DP Repeater 1 to 1 and 1 to 5 with optional level converter module The LSS PROFIBUS-DP repeaters 1 to 1 and 1 to 5 are used for coupling up to six PROFIBUS bus segments in RS 485 bus technology.

Mehr

Stromzwischenkreisumrichter Current Source Inverter (CSI)

Stromzwischenkreisumrichter Current Source Inverter (CSI) course " Conversion of electrical energy with power electronics " Stromzwischenkreisumrichter Current Source Inverter (CSI) Prof. Dr. Ing. Ralph Kennel (ralph.kennel@tum.de) Arcisstraße 21 80333 München

Mehr

Multicriterial Design Decision Making regarding interdependent Objectives in DfX

Multicriterial Design Decision Making regarding interdependent Objectives in DfX Overview Multicriterial Design Decision Making regarding interdependent Objectives in DfX S. Bauer The Design Process Support of the Design Process with Design for X Visualization of Decision Problems

Mehr

Studienkomitee A2 Transformers. Martin A. Stössl Siemens AG Österreich Transformers Weiz

Studienkomitee A2 Transformers. Martin A. Stössl Siemens AG Österreich Transformers Weiz Studienkomitee A2 Transformers Martin A. Stössl Siemens AG Österreich Transformers Weiz A2 Working Groups - Themenschwerpunkte 1. Zuverlässigkeit A2.37 Tx reliability survey A2.40 Copper sulphide long-term

Mehr

Cleanroom Fog Generators Volcano VP 12 + VP 18

Cleanroom Fog Generators Volcano VP 12 + VP 18 Cleanroom Fog Generators Volcano VP 12 + VP 18 Description & Functional Principle (Piezo Technology) Cleanrooms are dynamic systems. People and goods are constantly in motion. Further installations, production

Mehr