1. Installation 4. Connections between Load Sharer and IQ- Control Panel 5. Multi unit connection 6. Connection of more Load Sharers 6



Ähnliche Dokumente
Kurzanleitung um Transponder mit einem scemtec TT Reader und der Software UniDemo zu lesen

Softwareupdate-Anleitung // AC Porty L Netzteileinschub

Therefore the respective option of the password-protected menu ("UPDATE TUBE DATA BASE") has to be selected:

ZeppelinAir AirPlay -Konfiguration wireless

KIP Druckerstatus Benutzerhandbuch KIP Druckerstatus Installations- und Benutzerhandbuch

KURZANLEITUNG. Firmware-Upgrade: Wie geht das eigentlich?

MobiDM-App Handbuch für Windows Mobile

UWC 8801 / 8802 / 8803

Bedienungsanleitung Version 1.0

Contact 1600 QUICK REFERENCE GUIDE GUIDE D UTILISATION BEDIENUNGSANLEITUNG GUÍA DE REFERENCIA RÁPIDA GUIDA RAPIDA. CHANGING THE WAY


SanStore: Kurzanleitung / SanStore: Quick reference guide

CABLE TESTER. Manual DN-14003

Installation und Start der Software AQ2sp Installation and Start of the software AQ2sp

miditech 4merge 4-fach MIDI Merger mit :

Parameter-Updatesoftware PF-12 Plus

Das neue Volume-Flag S (Scannen erforderlich)

Registrierungsprozess des Boardgeräts (OBU) Inhalt Registrierung auf der Online-Benutzeroberfläche HU-GO

1. Hardware Configuration Hardware-Konfiguration Software-Konfiguration Software Configuration...4

English. Deutsch. niwis consulting gmbh ( manual NSEPEM Version 1.0

KONFIGURATION TECHNICOLOR TC7200

Restschmutzanalyse Residual Dirt Analysis

MailUtilities: Remote Deployment - Einführung

Version/Datum: Dezember-2006

RS232-Verbindung, RXU10 Herstellen einer RS232-Verbindung zwischen PC und Messgerät oder Modem und Messgerät

Anleitung für DT-TPC Tel Modul

NEWSLETTER. FileDirector Version 2.5 Novelties. Filing system designer. Filing system in WinClient

CONTROLLER RECEIVER REPEATER PAIRING SLIM CLIP

Bedienungsanleitung User Manual

HorstBox (DVA-G3342SD) Anleitung zur Einrichtung der Telefonie

FIRMWARE UPDATE TAPMOTION TD

GSM Scanner Bedienungsanleitung

SNr bis mit Gigabyte AMD K7 Mainboard. Konfiguration 7 und 7M

1 Registrieren Sie sich als Benutzer auf dem Televes. 2 Sobald ein Konto erstellt ist, können Sie auf das Portal

Anleitung zur Installation von Windows XP Professional und dem Multilanguage Interface

How to install freesshd

Preisliste für The Unscrambler X

Live Streaming => Netzwerk ( Streaming Server )

SMARTtill Server mit Manager

Readme-USB DIGSI V 4.82

8. Bintec Router Redundancy Protocol (BRRP) 8.1 Einleitung

p^db=`oj===pìééçêíáåñçêã~íáçå=

Bedienungsanleitung TIME IT. a Look Solutions 1 product

Auto-Provisionierung tiptel 30x0 mit Yeastar MyPBX

Handbuch. Artologik EZ-Equip. Plug-in für EZbooking version 3.2. Artisan Global Software

PeakTech Zeitprogramm erstellen über Excel - Beispiel / Timed programs with Excel Example

netscreens DS Smart Signage Display Setup

EMCO Installationsanleitung Installation instructions

Installationsanleitung Webserver - Datenkommunikation

DWA-140: Betrieb unter Mac OS X Über dieses Dokument. Vorbereitungen. Laden der Treiber aus dem Internet - 1 -

Ein reales Testumfeld bereitstellen - basierend auf einer Produktionsdatenbank (ohne eine neue Kopie zu erstellen)

4.) Geben Sie im Feld Adresse die IP Adresse des TDC Controllers ein. Die Standard Adresse lautet

M a i l C r e d i t. \\Burt\user\Soutschek\FP\Technik\Frankiermaschinen\00_PC Software\MailCredit\Anleitung MailCredit Installation.

USB-Stick (USB-Stick größer 4G. Es ist eine größere Partition notwendig als die eines 4GB Rohlings, der mit NTFS formatiert wurde)

GSM: Airgap Update. Inhalt. Einleitung

Monitor VIS 3xx Kurzanleitung

VPN / IPSec Verbindung mit dem DI 804 HV und dem SSH Sentinel

Wireless LAN Installation Windows XP

Installation des COM Port Redirectors

1.1. Apache / Tomcat via JK JNI ## THIS FILE MAY BE OVERRIDEN AT RUNTIME. MAKE SURE TOMCAT IS STOPED

UM ALLE DATEN ZU KOPIEREN. ZUNÄCHST die Daten des alten Telefons auf einen Computer kopieren

Klausur BWL V Investition und Finanzierung (70172)

Betriebsanleitung. Mikroprozessorgesteuerter Batterie-Kapazitätstester CAPTEST 1225 und 2425 Für 12V (0,3 A 25 A) oder 24V (0,3 A 25 A)

Werbemittel-Spezifikationen

Kurzanleitung. MEYTON Aufbau einer Internetverbindung. 1 Von 11

INSTALLATION DES ETHERNET MODEMS. Inhalt:

(1) (2) (3) (4) (5) (6) (7)

Konfiguration VLAN's. Konfiguration VLAN's IACBOX.COM. Version Deutsch

Network Controller TCP/IP

Einrichten eines Postfachs mit Outlook Express / Outlook bis Version 2000

v i r t u A L C O M P o r t s

Das Registrierungs- und Autorisierungsbüro von Autodesk schickt Ihnen die Lizenzdatei im Textformat per .

Softwareupdate für einzelne oder alle Teile der Maschinensoftware (bei normaler Betriebsbereitschaft der Bedieneinheit)

Einrichtung des WS_FTP95 LE

Windows Server 2012 R2 Essentials & Hyper-V

Kurzanleitung MicroLite II und DataSuite

S O L U T I O N S ::::: CSE-H55 Ethernet/RS422 Wandler. Installationsanleitung

Word-CRM-Upload-Button. User manual

300 MBIT WIRELESS ACCESS POINT ROUTER

10.6 Programmier-Exits für Workitems

Remote Control - LeCroy Oszilloskop WaveSurfer 3000 mit LabVIEW via VICP LAN-Schnittstelle

RL

Dokumentation zum Spielserver der Software Challenge

Tech Tips. Language selection. DVA-5205P Setup

GA-LCD-Monitor RTR-SET PV-Vision

Behaglichkeitsmessung mit neuem Messgerät 435 von testo AG

DEU. Royal Exclusiv Pumpen & Anlagenbau. Anleitung zur Netzwerk-Konfiguration Red Dragon 4 Pumpen. v1.0

Einrichten einer mehrsprachigen Webseite mit Joomla (3.3.6)

SETUP TOOL. Bedienungsanleitung User s Manual

Ein neues Outlook Konto können Sie im Control Panel über den Eintrag Mail erstellen.

NuVinci Harmony Software und Firmware. Anleitung in deutscher Sprache

Anleitung zur Inbetriebnahme eines SQ-Robotersystems

Quick Guide Home Network Mode

Dokumentation IBIS Monitor

Autorisierung von ArcGIS 10.3 for Server ohne Internetverbindung

Autorisierung von ArcGIS 10.3 for Server mit Internetverbindung

B e d i e n u n g s a n l e i t u n g N O R T E S K O N A X - 4

Netzwerk einrichten unter Windows

Technical Support Information No. 123 Revision 2 June 2008

Transkript:

TABLE OF CONTENTS 1. Installation 4 Connections 5 Connections between Load Sharer and IQ- Control Panel 5 Multi unit connection 6 Connection of more Load Sharers 6 2. Configuration 7 Menu structure 7 Select language 8 Network setup 8 Network statistics 8 Set reference meter 8 Select connected XRGI systems 8 Main menu 9 3. Function 9 3

The Load Sharer divides the required system output between the existing XRGI systems in power-controlled mode. It ensures that each XRGI system is started individually. This reduces the amount of start-up current required. A Load Sharer must be used if multiple XRGI systems are to work in power-controlled mode. In heat-controlled mode the Load Sharer is used to start each XRGI system up separately. A Load Sharer is installed as shown in Fig. 1. Up to four XRGI systems can be connected to one Load Sharer. Fig. 1 Reference meter max. 4 XRGI max. 20 m 230VAC max. 1200 m max. 4 XRGI max. 20 m 230VAC max. 10 x Load Sharer 1. INSTALLATION The Load Sharer may only be installed by authorized EC POWER specialists. The modules must be installed on a vibration-free base. A Load Sharer must be installed as shown in Fig. 1. Incorrect installation will cause errors! The Load Sharer is connected to the IQ-Control Panels via CHP 1-4 connections. For each XRGI system a six-core cable must be laid from the IQ-Control Panel to the Load Sharer. The XRGI systems do not need to be connected to the Load Sharer in any particular order. The reference meter (not included) is connected to the reference meter input on the Load Sharer. The reference meter may be polarized, so the wires must be connected correctly to avoid permanent damage. The Load Sharer is compatible with the following measurement types: 300/5, 600/5, 1.000/5, 1.200/5. Load Sharers are networked with one another by using a Q-Network Cable [SFTP (CAT 6) network cable]. Unused RJ45 plugs must be covered with RJ45 (8 x 8) ISDN network terminators. 4

Connections Fig. 2 NET CHP 1 CHP 2 CHP 3 CHP 4 Ref. Meter Pulse IN +24 V Start Pulse Generator Start Pulse Generator Start Pulse Generator Start Pulse Generator J N L Power supply (NET) 110-240V~ L = Live N = Neutral J = Earth Connections between Load Sharer and IQ- Control Panel Fig. 3 5

Multi unit connection Fig. 4 Connection of more Load Sharers Fig. 5 6

2. CONFIGURATION The Load Sharer is configured at the LCD display under the cover. Next to the LCD display there are four keys: Fig. 6 Use and to scroll through the menu. Use ESC to return to the menu and OK to select entries. Press OK and selection will flash. Press the cursor keys or to select the value required. Press OK/ESC to save the entry (the selection stops flashing). The following items can be selected: Language, network setup, network statistics, set reference meter, select XRGI systems connected, select MASTER and SLAVE. Network setup: The Load Sharer that is connected to the reference meter must be configured as MASTER. In systems with multiple Load Sharers any Load Sharers that are not connected to the reference meter must be configured as SLAVE. Network statistics: this function is used to monitor RS485 traffic and assess network stability. It is only relevant in systems with multiple Load Sharers. Selection of the XRGI systems connected: Up to four XRGI systems can be connected to one Load Sharer. All XRGI systems are configured the same way. Menu structure 7

Select language Press the key to select language: Press OK and the selected language flashes. Press or to select the desired language. Now press OK/ESC: the LCD display stops flashing, and the language selected is saved. Network setup Use to select from the menu: The Load Sharer linked to the reference meter must be configured as the MASTER. In installations with more than one Load Sharer, those Load Sharers not connected to the reference meter must be programmed as SLAVE. Press OK, MASTER/SLAVE is shown on the LCD display. Use or to make the selection you require. Press OK/ESC: the text will stop flashing and the status required is saved. Network statistics This function is used to monitor RS485 traffic and assess the network stability. It is only relevant in installations with more than one Load Sharer. Use OK/ESC to scroll through statistics. Set reference meter Press to select from the menu: Press OK: the menu starts flashing. Press or to select a given meter. Press OK/ESC: the setting is saved (stops flashing). Select connected XRGI systems Up to four modular CHP units can be connected to one Load Sharer. Each is configured the same way. Press to select from the menu: Press OK, the selected XRGI starts flashing. Press or to select the desired XRGI. Press OK/ESC: the setting is saved (stops flashing). 8

Main menu The main menu display varies, depending on your network settings. Master Displays total consumption. Press OK/ESC to scroll through the four connected XRGIs to display the results. Another Load Sharer's XRGIs can also be shown here: Slave Unit The menu displays the number of the secondary XRGI, which the master unit allocated automatically. Press OK/ESC to scroll through the secondary Load Sharer's four XRGIs: 3. FUNCTION In installations with 2 to 4 XRGI systems the Load Sharer ensures that the load is shared between the XRGI systems. The required output is covered with a minimum of systems. This maximises efficiency and hence requires fewer operating hours overall. The Load Sharer passes on the information of the desired output to the next XRGI system that is ready for operation. If necessary, it then starts up several XRGI systems. The Load Sharer has a built-in sequential start to ensure that each XRGI system starts separately. This keeps the start-up current and cable load low. Fig. 7 Last auf drei Anlagen verteilt 70 Leistung in kw 60 50 40 30 20 10 0 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Bedarf PU3 PU2 PU1 Zeit in Std. In a sequential start the first XRGI system is given 10 seconds to start up. If it does not, the Load Sharer waits another 10 seconds before it starts the next unit. When that XRGI system starts, the following system will not be released for at least a minute. This means that the first XRGI system generates the current to start further systems. 9

Inhaltsverzeichnis 1. Installation 12 Anschlüsse 13 Verbindungen zwischen Load Sharer und IQ-Schaltschrank 13 Multi-Unit-Verbindung 14 Verbindung mehrerer Load Sharer 14 2. Konfiguration 15 Menüstruktur 15 Sprachauswahl 16 Netzwerkeinrichtung 16 Netzwerkstatistik 16 Einstellen des Referenzzählers 16 Auswahl der angeschlossenen BHKW-Einheiten 16 Hauptmenü 17 3. Funktion 17 11

Der Load Sharer teilt die erforderliche Anlagenleistung auf vorhandene XRGI-Anlagen im stromgeführten Modus auf. Er stellt sicher, dass jede XRGI-Anlage einzeln startet. Dies reduziert den Bedarf an Anlaufstrom. Ein Load Sharer kommt zum Einsatz, wenn mehrere Power Units im stromgeführten Modus arbeiten sollen. Im wärmegeführten Modus wird der Load Sharer eingesetzt, um jede XRGI-Anlage einzeln zu starten. Ein Load Sharer wird gemäß Abb.1 installiert (maximal vier XRGI-Anlagen pro Load Sharer). Abb. 1 Referenzzähler max. 4 XRGI max. 20 m 230VAC max. 1200 m max. 4 XRGI max. 20 m 230VAC max. 10 x Load Sharer 1. INSTALLATION Der Load Sharer ist ausschließlich durch autorisiertes EC POWER-Fachpersonal zu montieren. Die Module müssen auf einen vibrationsfreien Untergrund montiert werden. Ein Load Sharer muss gemäß Abb. 1 angeschlossen werden. Abweichungen verursachen Betriebsstörungen! Der Load Sharer wird mit den IQ-Schaltschränken über die Anschlüsse CHP1-4 verbunden. Für jede XRGI-Anlage muss ein sechsadriges Kabel vom IQ-Schaltschrank zum Load Sharer verlegt werden. Die XRGI-Anlagen können in beliebiger Reihenfolge am Load Sharer angeschlossen werden. Der Referenzzähler (nicht im Lieferumfang enthalten) wird am Eingang Ref.Meter des Load Sharers angeschlossen. Der Stromzähler kann Polarität aufweisen die Leitungen müssen deshalb korrekt am Pulsausgang angeschlossen werden, um dauerhafte Schäden zu vermeiden. Der Load Sharer ist kompatibel mit den folgenden Messtypen: 300/5, 600/5, 1.000/5, 1.200/5 Die Vernetzung von Load Sharern untereinander erfolgt durch ein Q-Netzwerkkabel (SFTP (CAT 6) Netzkabel). Ungenutzte RJ45-Stecker müssen mit einem Netzabschluss RJ45 (8 x 8) ISDN abgedeckt werden. 12

Anschlüsse Abb. 2 NET CHP 1 CHP 2 CHP 3 CHP 4 Ref. Meter Pulse IN +24 V Start Pulse Generator Start Pulse Generator Start Pulse Generator Start Pulse Generator J N L Power supply (NET) 110-240V~ L = Live N = Neutral J = Earth Verbindungen zwischen Load Sharer und IQ-Schaltschrank Abb. 3 13

Multi-Unit-Verbindung Abb. 4 Verbindung mehrerer Load Sharer Abb. 5 14

2. KONFIGURATION Der Load Sharer wird am Display unter dem Deckel eingestellt. Neben dem LCD-Display befinden sich vier Tasten: Abb. 6 Benutzten Sie und, um im Menü zu blättern. Mit ESC gehen Sie im Menü zurück und mit OK können Sie eintasten. Drücken Sie OK und die Auswahl blinkt. Stellen Sie den gewünschten Wert durch Betätigung der Pfeiltasten oder ein. Drücken Sie OK/ESC, um die Einstellung zu speichern (die Auswahl blinkt nicht mehr). Folgende Punkte können gewählt werden: Sprachauswahl, Netzwerkeinrichtung, Netzwerkstatistik, Einstellen des Referenzzählers, Auswahl der angeschlossenen XRGI-Einheiten, Auswahl von "MASTER"/" SLAVE". Netzwerkeinrichtung: Der Load Sharer, der mit dem Referenzzähler verbunden ist, muss als "MASTER" konfiguriert werden. Bei Installationen mit mehr als einem Load Sharer müssen die Load Sharer ohne Anschluss an den Referenzzähler als "SLAVE" programmiert werden. Netzwerkstatistik: Diese Funktion dient zur Kontrolle des RS485-Verkehrs und zur Abschätzung der Netzwerkstabilität und ist nur bei Installationen mit mehr als einem Load Sharer relevant. Auswahl der angeschlossenen XRGI-Anlagen: Maximal vier XRGI-Anlagen können an einen Load Sharer angeschlossen werden. Die Konfiguration erfolgt für alle XRGI-Anlagen auf die gleiche Weise. Menüstruktur 15

Sprachauswahl Nach Drücken der -Taste erscheint die Sprachauswahl: Drücken Sie OK und die Auswahl der Sprache blinkt. Drücken Sie oder, um die gewünschte Sprache auszuwählen. Drücken Sie dann OK/ESC. Das Blinken endet und die ausgewählte Sprache wird gespeichert. Netzwerkeinrichtung Bitte wählen Sie mit aus dem Menü: Der Lastverteiler, der mit dem Referenzzähler verbunden ist, muss als MASTER konfiguriert werden. Bei Installationen mit mehr als einem Lastverteiler müssen die Lastverteiler ohne Anschluss an den Referenzzähler als SLAVE programmiert werden. Drücken Sie OK; es leuchtet MASTER/SLAVE auf. Benutzen Sie oder, um die gewünschte Auswahl zu treffen. Drücken Sie OK/ESC; der Text hört auf zu blinken und der geforderte Zustand wird gespeichert. Netzwerkstatistik Diese Funktion dient zur Kontrolle des RS485-Verkehrs und zur Abschätzung der Netzwerkstabilität und ist nur bei Installationen mit mehr als einem Lastverteiler relevant. Um die statistischen Werte durchzublättern, benutzen Sie bitte OK/ESC. Einstellen des Referenzzählers Drücken Sie, um das Menü auszuwählen: Drücken Sie OK und der eingestellte Zähler blinkt. Um einen bestimmten Zähler auszuwählen, drücken Sie oder. Drücken Sie OK/ESC; die Einstellung ist gespeichert und blinkt nicht mehr. Auswahl der angeschlossenen BHKW-Einheiten Maximal vier XRGI-Anlagen können an einen Lastverteiler angeschlossen werden. Die Konfiguration erfolgt für alle XRGI- Anlagen auf die gleiche Weise. Drücken Sie, um den Menüpunkt auszuwählen: Drücken Sie OK und die gewählte XRGI-Anlage blinkt. Um die entsprechende XRGI-Anlage auszuwählen, drücken Sie oder. Drücken Sie OK/ESC; die Einstellung ist gespeichert und blinkt nicht mehr. 16

Hauptmenü Abhängig von der Netzwerkeinstellung zeigt das Hauptmenü verschiedene Informationen: Master Der Gesamtverbrauch wird angezeigt. Drücken Sie OK/ESC, um sich durch die vier XRGI zu blättern, in denen die Ergebnisse gezeigt werden. Die XRGI eines weiteren Lastverteilers können hier ebenfalls angezeigt werden: Slave-Einheit Die Nummer des automatisch von der Master-Einheit zugeordneten XRGI wird hier angezeigt. Drücken Sie OK/ESC, um durch die vier XRGI des untergeordneten Lastverteilers zu blättern: 3. FUNKTION Bei Installationen mit 2 bis 4 XRGI-Anlagen sorgt der Load Sharer dafür, dass die Last zwischen den XRGI-Anlagen verteilt wird. Die benötigte Leistung wird mit einem Minimum von Anlagen abgedeckt. Dies ermöglicht den besten Wirkungsgrad und so werden insgesamt weniger Betriebsstunden benötigt. Der Load Sharer gibt die Informationen der gewünschten Leistung an die nächste betriebsbereite XRGI-Anlage weiter und prüft, wie groß die gewünschte Leistung ist. Falls erforderlich, startet er dann mehrere XRGI-Anlagen. 70 60 50 40 30 20 10 Leistung in kw Last auf drei Anlagen verteilt Abb. 7 Der Load Sharer hat einen eingebauten Sequenzstart, der 0 sicherstellt, dass jede XRGI-Anlage einzeln startet. Der Anlaufstrom 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 und die Kabelbelastung werden somit gering ge- halten. Bedarf PU3 PU2 PU1 Zeit in Std. Beim Sequenzstart werden der ersten XRGI-Anlage 10 Sekunden gegeben, um zu starten. Sollte diese nicht starten, wartet der Load Sharer weitere 10 Sekunden bis zur Freigabe der zweiten Einheit. Wenn die zweite XRGI-Anlage startet, wird die nächste Freigabe frühestens nach einer Minute gegeben. Dadurch produziert die erste XRGI-Anlage den Strom für den Start weiterer. 17

EC POWER A /S Samsøvej 25 DK 8382 Hinnerup Tel.: (+45) 87 434 100 Fax: (+45) 87 434 101 E-mail: info@ecpower.eu Web: www.ecpower.eu