Instructions for Series NRX Neutral Current Sensor Type NF

Größe: px
Ab Seite anzeigen:

Download "Instructions for Series NRX Neutral Current Sensor Type NF"

Transkript

1 effective January 2011 supersedes IL H01 Series NR Instructions for Series NR Neutral Current Sensor Type NF Instructions apply to: Series NR, Type NF Frame ANSI, UL1066, UL489 / IEC, IZM16, IZM91 Warning (1) Only qualified electrical personnel should be permitted to work on the equipment. (2) Always de-energize primary and secondary circuits if a circuit breaker cannot be removed to a safe work location. (3) Drawout circuit breakers should be levered (racked) out to the Disconnect position. (4) All circuit breakers should be switched to the off position and mechanism springs discharged. Failure to follow these steps for all procedures described in this instruction leaflet could result in death, bodily injury, or property damage. Warning The instructions contained in this IL and on product labels have to be followed. Observe the Five Safety Rules: Disconnecting Ensure that devices cannot be accidentally restarted Verify isolation from the supply Earthing and short-circuiting Covering or providing barriers to adjacent live parts Disconnect the equipment from the supply. Use only authorized spare parts in the repair of the equipment. The specified maintenance intervals as well as the instructions for repair and exchange must be strictly adhered to prevent injury to personnel and damage to the switchboard.

2 effective January 2011 Instructions for Series NR Neutral Current Sensor Type NF Section 1: Neutral Current Sensor Installation Ground Fault Trip Units detect ground fault currents through Residual Sensing. A different, round, torroidal sensor is required for source ground or zero sequence sensing. All further information is for residual ground fault sensing method only. If the system neutral is grounded and residual ground fault is desired, but no phase to neutral loads are used, a neutral current sensor is not necessary. In that case, no additional connections are required to circuit breaker secondary contacts. If the system neutral is grounded and phase to neutral loads are used, then the neutral current sensor (see Figure 2 and 3) must be used to account for this load in the residual ground fault sensing. It has the same turns ratio as the phase current sensors in the Series NR circuit breaker. The neutral sensor is an air core design and can be used with all Type NF rating plugs (Figure 1). IMPOrtant The polarity of the sensor connections is critical. Always observe the polarity markings on the installation drawings. The polarity markings are identified as white dots on the transformers. To insure correct ground fault equipment performance, conduct field tests to comply with National Electric Code requirements under Article C. See Performance Testing instructions on following pages. Section 2: Performance Testing For Ground Fault Circuit Breakers Code Requirements In the United States of America and certain other countries it is required that any ground fault protection system be performance tested when first installed (National Electric Code under Article C). Conduct tests in accordance with the approved instructions provided with the equipment. Make a written record of this test and make the results available to the authority having inspection jurisdiction. Standards Requirements In addition to the basic performance requirements stated above, UL Standard No requires that certain minimum instructions accompany each ground fault protection system. General Test Instructions The interconnect system shall be evaluated in accordance with the equipment assembler s detailed instruction by qualified personnel. The polarity of the neutral sensor connection (if used) must agree with equipment assembler s detailed instructions to avoid improper operations following apparently correct simulated test operations. Where a question exists, consult the specifying engineer and/or equipment assembler ,9 mm ,8 mm ,0 mm Torque to 50 lb ft ±3 67,8 Nm ± 4, ,9 mm ,9 mm ,6 mm Polarity Markings Torque to 20 lb in ±2 27,1 Nm ±2, at top 69,9 mm at top 57,2 mm ,6 mm T/Potting ,5 mm T/Conductor mm ,9 mm ,0 mm ,2 mm at Base 152,4 mm at base 59,9 mm at base 77,2 mm Figure 1. Sensor Installation Information - Type NF 2

3 Instructions for Series NR Neutral Current Sensor Type NF IL E effective January 2011 The grounding points of the system shall be verified to determine that ground paths do not exist that would bypass the sensors. High-voltage testers and resistance bridges may be used. N L C R Using a low voltage (0-24v) high current AC source, apply a test current of 125% of the ground fault pick-up setting through one phase of the circuit breaker as displayed in Figures 4 and 7. This should cause the breaker to trip in less than 1 second, and if an alarm indicator is supplied, it should operate. Reset the breaker and the alarm indicator. Repeat the test on the other two phases. If the system is a 4-wire system with a neutral current sensor, apply the same current as described above through one phase of the breaker, returning through the neutral sensor, as displayed in Figures 5 and 8. The breaker should not trip and the alarm indicator, if supplied, should not operate. Repeat the test on the other two phases. Neutral Sensor If the system is a 3-wire system with no neutral current sensor, apply the same current as described above through any two phases of the breaker with the connections as displayed in Figures 6 and 9. The breaker should not trip and the alarm indicator, if supplied, should not operate. Repeat the test using the other two combinations of breaker phases. Record the test results on the test form provided with the equipment. Figure 2. Neutral Current Sensor Application (NEMA) N L C R CAUTION FIELD TESTING SHOULD BE USED FOR FUNCTIONAL TESTING, NOT FOR FIELD CALIBRATION. IF TEMPORARY CONNECTIONS WERE MADE FOR THE PURPOSE OF CONDUCTING TESTS, RESTORE TO PROPER OPERATING CONDITIONS BEFORE RETURNING THE BREAKER TO SERVICE. WARNING ELECTRICAL SHOCK OR BURN INJURY CAN OCCUR WHEN WORKING ON POWER SYSTEMS. ALWAYS TURN OFF POWER SUPPLYING CIRCUIT BREAKER BEFORE CONDUCTING TESTS. TEST OUT OF THE CELL, IF POSSIBLE. Neutral Sensor Figure 3. Neutral Current Sensor Application (IEC) Note: Since the ground fault circuit breakers derive their operating power from the phase current and not from the neutral current, passing current through the neutral sensor only will not properly test the ground fault feature. EATON CORPORATION 3

4 effective January 2011 Instructions for Series NR Neutral Current Sensor Type NF Low Voltage Low Voltage Low Voltage Current Limiting Resistor (if required) Current Limiting Resistor (if required) Current Limiting Resistor (if required) Figure 4. Connections for Ground Fault Trip Test (NEMA) Figure 5. Connections for Ground Fault No-Trip Test with a 4 Wire System (NEMA) Figure 6. Connections for Ground Fault No-Trip Test with a 3 Wire System (NEMA) Low Voltage Low Voltage Low Voltage Current Limiting Resistor (if required) Current Limiting Resistor (if required) Current Limiting Resistor (if required) Figure 7. Connections for Ground Fault Trip Test (IEC) Figure 8. Connections for Ground Fault No-Trip Test with a 4 Wire System (IEC) Figure 9. Connections for Ground Fault No-Trip Test with a 3 Wire System (IEC) 4

5 Instructions for Series NR Neutral Current Sensor Type NF Instruction Leaflet IL E effective January

6 effective January 2011 Instructions for Series NR Neutral Current Sensor Type NF Disclaimer of warranties and limitation of liability The information, recommendations, descriptions, and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein. The information contained in this manual is subject to change without notice. Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA United States 877-ETN-CARE ( ) Eaton.com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL EH02 January 2011 Power Chain Management is a registered Trademark of Eaton Corporation All other Trademarks are property of their respective owners. 6

7 gültig ab Januar 2011 ersetzt IL H01 Series NR Montageanweisung für Series NR Neutralwandler - Baugröße NF Die Montageanweisung ist für folgende Baugrößen gültig: Series NR, Type NF Frame ANSI, UL1066, UL489 / IEC, IZM16, IZM91 warnung (1) Die Instandhaltung darf nur durch entsprechend elektrontechnisch qualifiziertes Personal erfolgen. (2) Vor Beginn der Arbeiten muss der spannungsfreie Zustand der Schaltanlage hergestellt und während der Arbeiten sichergestellt sein. (3) Schalter in Ausfahrtechnik müssen in Trennstellung gefahren werden. (4) Die Schalter sind auf AUS zu stellen und der Federspeicher ist zu entspannen. Beim Betrieb elektrischer Geräte stehen zwangsläufig bestimmte Teile dieser Geräte unter gefährlicher Spannung. UnsachgemäSSer Umgang mit diesen Geräten kann deshalb zu Tod oder schweren Körperverletzungen sowie erheblichen Sachschäden führen. warnung Beachten Sie bei InstandhaltungsmaSSnahmen an diesem Gerät alle in dieser awa und auf dem Produkt selbst aufgeführten Hinweise. Die fünf Sicherheitsregeln sind einzuhalten Freischalten Gegen Wiedereinschalten sichern Spannungsfreiheit feststellen Erden und KurzschlieSSen Benachbarte, unter Spannung stehende teile abdecken oder abschranken Das Gerät ist vom Netz zu trennen. Es dürfen nur vom Hersteller zugelassene Ersatzteile verwendet werden. Die vorgeschriebenen Wartungsintervalle sowie die Anweisungen für Reparatur und Austausch sind unbedingt einzuhalten, um Schäden an Personen und Anlagen zu vermeiden.

8 gültig ab Januar 2011 Montageanweisung für Series NR Neutralwandler - Baugröße NF Abschnitt 1: Installation des Neutralwandlers Die Fehlerstrommessung ist die Standardmethode für Erdschlussmessungen in NR-Leistungsschaltern. Für die Fehlerstromquellenmessung oder die Nullmessung wird ein anderer Wandler-Typ benötigt. Die folgenden Informationen betreffen nur die Fehlerstrommessung. Wenn das Neutralsystem geerdet ist und als Messmethode die Fehlerstrommessung verwendet wird, aber keine Phase zu Neutrallasten verwendet wird, dann ist der Einsatz eines Neutralwandlers nicht erforderlich. In diesem Falle sind auch keine weiteren Verbindungen zu den Steuerleitungsanschlüssen nötig. Wenn das Neutralsystem geerdet ist und eine Phase zu Neutrallasten verwendet wird, dann ist der Einsatz des Neutralwandlers (siehe Abbildung 2 und 3) erforderlich. Dieser hat das gleiche Verhältnis wie die Stromwandler. Der Neutralwandler hat einen Luftkern und kann mit allen für die Baugröße NF kompatiblen Bemessungsstrommodulen verwendet werden (siehe Abbildung 1). Abschnitt 2: Funktionsprüfung für Leistungsschalter mit Erdschlussschutz Prüfanforderungen für Nordamerika und andere Länder In Nordamerika und bestimmten anderen Ländern ist es vorgeschrieben, dass jedes Erdschlussgerät vor der ersten Inbetriebnahme einer Funktionsprüfung unterzogen wird (siehe National Electric Code Artikel C). Führen Sie die Prüfung gemäß der genehmigten und mit der Ausrüstung gelieferten Anleitung durch und fertigen Sie einen schriftlichen Bericht über die Durchführung des Tests an. Normen Als Zusatz zu den grundlegenden von der NEC vorgeschriebenen Leistungsanforderungen wird durch UL -Norm 1053 gefordert, dass jedem Erdschlussschutzsystem eine Anleitung mit einem bestimmten Mindestumfang beigelegt werden muss. ACHTUNG Fehlerhaftes AnschlieSSen der Stromwandler kann zu Fehlauslösungen führen. Beachten Sie immer die Polmarkierungen der Montagepläne. DIe Polmarkierungen sind als weisse Punkte auf den Wandlern markiert. Führen Sie zur Sicherstellung des ordnungsgemässen Betriebs der Erdschlussausrüstung Vor-Ort-Tests gemäss National Elecetric Code (NEC) C durch ,9 mm ,8 mm ,0 mm Anziehen auf 50 lb ft ±3 67,8 Nm ± 4, ,9 mm ,8 mm ,6 mm Polmarkierungen Anziehen auf 20 lb in ±2 27,1 Nm ±2, Oberseite 69,9 mm Oberseite 57,2 mm ,6 mm T/Potting ,5 mm T/Conductor mm ,9 mm ,0 mm ,2 mm Unterseite 152,4 mm Unterseite 59,9 mm Unterseite 77,2 mm Abbildung 1. Abmessungen Neutralwandler - Baugröße NF 2

9 Montageanweisung für Series NR Neutralwandler - Baugröße NF Instruction Leaflet IL E gültig ab Januar 2011 Allgemeine Prüfhinweise Das vernetzte System muss von qualifizierten Fachleuten gemäß den detaillierten Anweisungen des Geräteherstellers beurteilt werden. Um einen nicht ordnungsgemäßen Betrieb nach offensichtlich korrekt simulierten Prüfoperationen zu vermeiden, muss die Polarität der Neutralwandlerkontakte (falls verwendet) mit den detaillierten Anweisungen des Geräteherstellers übereinstimmen. Wenden Sie sich bei Fragen an den zuständigen Ingenieur und/oder den Gerätehersteller. Prüfen Sie die Erdungspunkte des Systems mithilfe von Hochspannungsprüfern und Widerstandsbrücken, um sicherzustellen, dass keine an den Wandlern vorbeiführenden Erdleitungen existieren. N L C R Verwenden Sie eine Niederspannungs- (0 bis 24 V), Hochstrom-AC- Quelle, um einen Prüfstrom von 125 Prozent des Ansprechwertes des Erdschlussauslösers an eine Phase des Leistungsschalters anzulegen (siehe Abbildung 4 und 7). Dies sollte zu einer Auslösung des Schalters innerhalb einer Sekunde führen und die Alarmanzeige (falls vorhanden) aktivieren. Setzen Sie Schalter und Alarmanzeige in den Ausgangszustand zurück. Wiederholen Sie diese Prüfung für die anderen beiden Phasen. Um ein 4-Poliges System mit einem Neutralwandler zu prüfen, legen Sie denselben Strom (s.o.) an eine Phase des Schalters mit Rückführung durch den Neutralwandler an (siehe Abbildung 5 und 8). Der Schalter sollte nicht ausgelöst werden und die Alarmanzeige (falls vorhanden) sollte nicht in Betrieb sein. Um ein 3-Poliges System ohne Neutralwandler zu prüfen, legen Sie denselben Strom (s.o.) an zwei beliebige Phasen des Schalters an (siehe Abbildung 6 und 9). Der Schalter sollte nicht ausgelöst werden und die Alarmanzeige (falls vorhanden) sollte nicht in Betrieb sein. Wiederholen Sie diese Prüfung für die anderen beiden möglichen Phasenkombinationen Halten Sie die Prüfergebnisse auf den Prüfformular fest. Neutralwandler Warnung BEI DER ARBEIT AN STROMVERSORGUNGSSYSTEMEN BESTEHT IMMER DIE GEFAHR EINES ELEKTRISCHEN SCHLAGS ODER EINES ELEKTROBRANDS. schalten SIE VOR DURCHFÜHRUNG DER Prüfungen IMMER DEN schalter FÜR DIE STROMVERSORGUNG AB. Entfernen SIe den Schalter wenn möglich immer aus der Kassette. Abbildung 2. Neutralwandler Anwendung (NEMA) N L C R Warnung Funktionsprüfungen sollten nur zur Sicherstellung der Funktionalität des Leistungsschalters vorgenommen werden, Nicht zur Kalibrierung des Schalters. Stellen Sie nach der Funktionsrpüfung alle EInstellungen des Leistungsschalters in ihren Ausgangszustand zurück und entfernen Sie alle für die Prüfung vorgenommenen Verbindungen zu den Prüfgeräten bevor der Schalter wieder in Betrieb genommen wird. Neutralwandler Abbildung 3. Neutralwandler Anwendung (IEC) AAnmerkung: Da Leistungsschalter mit Erdschlussschutz ihren Betriebsstrom aus den Stromwandlern und nicht aus dem Neutralwandler beziehen, reicht es bei einer Funktionsprüfung nicht aus nur Strom durch den Neutralwandler zu leiten, um den Erdschlussschutz zu prüfen. 3

10 gültig ab Januar 2011 Montageanweisung für Series NR Neutralwandler - Baugröße NF Niederspannungs- Quelle Niederspannungs- Quelle Niederspannungs- Quelle Strombegrenzungs- Widerstand (falls nötig) Strombegrenzungs- Widerstand (falls nötig) Strombegrenzungs- Widerstand (falls nötig) Abbildung 4. Verbindungen für Erdschlussauslöseprüfungen (NEMA) Abbildung 5. Verbindungen für Erdschlussprüfung ohne Auslösung bei 4-poligen System (NEMA) Abbildung 6. Verbindungen für Erdschlussprüfung ohne Auslösung bei 3-poligen System (NEMA) Niederspannungs- Quelle Niederspannungs- Quelle Niederspannungs- Quelle Strombegrenzungs- Widerstand (falls nötig) Abbildung 7. Verbindungen für Erdschlussauslöseprüfungen (IEC) Strombegrenzungs- Widerstand (falls nötig) Abbildung 8. Verbindungen für Erdschlussprüfung ohne Auslösung bei 4-poligen System (IEC) Strombegrenzungs- Widerstand (falls nötig) Abbildung 9. Verbindungen für Erdschlussprüfung ohne Auslösung bei 3-poligen System (IEC) 4

11 Montageanweisung für Series NR Neutralwandler - Baugröße NF Instruction Leaflet IL E gültig ab Januar

12 gültig ab Januar 2011 Montageanweisung für Series NR Neutralwandler - Baugröße NF Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA United States 877-ETN-CARE ( ) Eaton.com 2011 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL EH02 Januar 2011 Power Chain Management is a registered Trademark of Eaton Corporation All other Trademarks are property of their respective owners. 6

Montageanweisung für Series NRX Rückseitige Hauptanschlüsse

Montageanweisung für Series NRX Rückseitige Hauptanschlüsse Series NRX Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX, Type RF Frame IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES PERSONAL

Mehr

Installation and removal instructions for Series NRX fixed breaker mounting feet

Installation and removal instructions for Series NRX fixed breaker mounting feet Instructional Leaflet IL01301030E Effective December 2010 Supersedes June 2010 IL01301030EH03 Installation and removal instructions for Series NRX fixed breaker mounting feet Instructions apply to: Series

Mehr

Installation and Removal Instructions for Series NRX Rating Plug

Installation and Removal Instructions for Series NRX Rating Plug effective May 2011 Series NRX Installation and Removal Instructions for Series NRX Rating Plug Instructions apply to: Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91 Series NRX, Type

Mehr

Installation and Removal Instructions for Series NRX Drawout Cassette Primary IP20 Safety Shutters

Installation and Removal Instructions for Series NRX Drawout Cassette Primary IP20 Safety Shutters Installation and Removal Instructions for Series NRX Drawout Cassette Primary IP20 Safety s Instructions apply to: effective March 2011 Series NRX Series NRX, Type RF Frame IEC, IZMX40 WARNING (1) ONLY

Mehr

Bedienungs- und Montageanweisung für Türverriegelung

Bedienungs- und Montageanweisung für Türverriegelung Bedienungs- und Montageanweisung für Die Montageanweisung ist für folgende Baugrößen gültig: Serie NRX Serie NRX, Typ Baugröße RF IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND

Mehr

Montageanweisung für Series NRX Schaltspielzähler

Montageanweisung für Series NRX Schaltspielzähler Series NRX Diese Montageanweisung ist für folgende Baugrößen gültig: Series NRX, Type RF Frame IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES PERSONAL

Mehr

Installation and Removal Instructions for Series NRX Pushbutton Cover Kit

Installation and Removal Instructions for Series NRX Pushbutton Cover Kit effective June 2011 Series NRX Installation and Removal Instructions for Series NRX Pushbutton Cover Kit Instructions apply to: Series NRX, Type RF Frame IEC, IZMX40 Warning (1) Only qualified electrical

Mehr

Montageanweisung für Series NRX CES Verriegelung Sicheres AUS

Montageanweisung für Series NRX CES Verriegelung Sicheres AUS Series NRX Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91 Series NRX, Type RF Frame IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG

Mehr

Montageanweisungen für Schaltspielzähler

Montageanweisungen für Schaltspielzähler Gültig ab September 2010 Ersetzt Juni 2010 IL01301011EH03 Montageanweisungen für Schaltspielzähler NRX (IZMX16/IZM91) WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES

Mehr

Front-mounted standard terminal kits on IZM low voltage fixed circuit breakers and cassettes

Front-mounted standard terminal kits on IZM low voltage fixed circuit breakers and cassettes Effective May 2010 2C13997H02 Front-mounted standard terminal kits on IZM low voltage fixed circuit breakers and cassettes warning (1) Only qualified electrical personnel should be permitted to work on

Mehr

Montageanweisung für NRX Ronis Verriegelung Sicheres AUS

Montageanweisung für NRX Ronis Verriegelung Sicheres AUS Instruction Leaflet IL01301040E Series NRX Montageanweisung für NRX Ronis Verriegelung Sicheres AUS Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX, Type NF Frame ANSI, UL1066, UL489

Mehr

Instruction Leaflet IL E Montageanweisung für Series NRX Hilfsschalter

Instruction Leaflet IL E Montageanweisung für Series NRX Hilfsschalter Series NRX Montageanweisung für Series NRX Hilfsschalter Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX, Type NF Frame ANSI, UL066, UL489 / IEC, IZMX6, IZM9 Series NRX, Type RF Frame

Mehr

Montageanweisung für Series NRX Fehlerstromquelllen- und Summenstromwandler

Montageanweisung für Series NRX Fehlerstromquelllen- und Summenstromwandler ersetzt Januar 2011 Die Montageanweisung ist für folgende Baugrößen gültig: Series RX Series RX, Type F Frame ASI, UL1066, UL489 / IEC, IZMX16, IZM91 Series RX, Type RF Frame IEC, IZMX40 (1) DIE ISTADHALTUG

Mehr

Montageanweisung für Series NRX Mechanische 3-Wege Verriegelung für Ausfahrtechnik

Montageanweisung für Series NRX Mechanische 3-Wege Verriegelung für Ausfahrtechnik Instruction Leaflet IL01301070E Series NRX für Ausfahrtechnik Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91 WARNUNG (1) DIE

Mehr

Installation Instructions for Series NRX Communication Adapter Modules

Installation Instructions for Series NRX Communication Adapter Modules Instructional Leaflet IL01301077E effective May 2012 Series NRX Installation Instructions for Series NRX Communication Adapter Modules Instructions apply to: Series NRX, Type NF Frame ANSI, UL1066, UL489/IEC

Mehr

Montageanweisung für Series NRX Mechanische 2-Wege Verriegelung für Ausfahrtechnik

Montageanweisung für Series NRX Mechanische 2-Wege Verriegelung für Ausfahrtechnik Instruction Leaflet IL01301069E Montageanweisung für Series NRX für Ausfahrtechnik Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC,

Mehr

Mechanische Verriegelung über zwei Leistungsschalter, Festeinbau IZMX- MIL2C-F

Mechanische Verriegelung über zwei Leistungsschalter, Festeinbau IZMX- MIL2C-F Instruction Leaflet IL01301071E Mechanische Verriegelung über zwei - Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91

Mehr

Installation/Removal Instructions for Series NRX Pushbutton Cover Kit

Installation/Removal Instructions for Series NRX Pushbutton Cover Kit Instructional Leaflet IL01301041E Effective September 2012 Supersedes December 2010 IL01301041EH04 Installation/Removal Instructions for Instructions apply to: Series NRX, Type NF Frame ANSI, UL1066, UL489/IEC

Mehr

Electrical testing of Bosch common rail piezo injectors

Electrical testing of Bosch common rail piezo injectors Applies to generation CRI 3: Bosch 10-position order number 0 445 115 = CRI 3-16 (CRI 3.0) 1600 bar 0 445 116 = CRI 3-18 (CRI 3.2) 1800 bar 0 445 117 = CRI 3-20 (CRI 3.3) 2000 bar Tools required: Hybrid

Mehr

Montageanweisung für Series NRX Ausgelöstmelder

Montageanweisung für Series NRX Ausgelöstmelder Serie NRX Die Montageanweisung ist für folgende Baugrößen gültig: Serie NRX, Typ RF IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES PERSONAL ERFOLGEN.

Mehr

ALL1688PC. Benutzerhandbuch. Passiver Powerline Verbindung (Home Plug Gerät) Phasenkoppler (Hutschienen Version)

ALL1688PC. Benutzerhandbuch. Passiver Powerline Verbindung (Home Plug Gerät) Phasenkoppler (Hutschienen Version) ALL1688PC Passiver Powerline Verbindung (Home Plug Gerät) Phasenkoppler (Hutschienen Version) Benutzerhandbuch Legal Notice 2011 All rights reserved. No part of this document may be reproduced, republished,

Mehr

Montageanweisung für Series NRX Positionsmeldeschalter

Montageanweisung für Series NRX Positionsmeldeschalter Ersetz Marz 2012 Die Montageanweisung ist für folgende Baugrößen gültig: Serie NRX Series NRX, Type RF Frame IEC, IZMX40 n WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES

Mehr

Electrical testing of Bosch common rail solenoid valve (MV) injectors

Electrical testing of Bosch common rail solenoid valve (MV) injectors Applies to MV injector, generation: -CRI 1.0 / 2.0 / 2.1 / 2.2 -CRIN 1 / 2 / 3, with K oder AK plug Bosch 10-position order number Bosch-Bestellnummer CRI: 0 445 110 xxx Bosch-Bestellnummer CRIN: 0 445

Mehr

SnagIt 9.0.2. Movable Type Output By TechSmith Corporation

SnagIt 9.0.2. Movable Type Output By TechSmith Corporation SnagIt 9.0.2 By TechSmith Corporation TechSmith License Agreement TechSmith Corporation provides this manual "as is", makes no representations or warranties with respect to its contents or use, and specifically

Mehr

Installation and Operation Instructions for Lev-In Door Interlock

Installation and Operation Instructions for Lev-In Door Interlock Instruction Leaflet IL01301066E Installation and Operation Instructions for Lev-In Door Interlock Instructions apply to: effective September 2012 Series NRX Series NRX, Type RF Frame IEC, IZMX40 WARNING

Mehr

SnagIt 9.0.2. LiveJournal Output By TechSmith Corporation

SnagIt 9.0.2. LiveJournal Output By TechSmith Corporation SnagIt 9.0.2 By TechSmith Corporation TechSmith License Agreement TechSmith Corporation provides this manual "as is", makes no representations or warranties with respect to its contents or use, and specifically

Mehr

Release Notes BRICKware 7.5.4. Copyright 23. March 2010 Funkwerk Enterprise Communications GmbH Version 1.0

Release Notes BRICKware 7.5.4. Copyright 23. March 2010 Funkwerk Enterprise Communications GmbH Version 1.0 Release Notes BRICKware 7.5.4 Copyright 23. March 2010 Funkwerk Enterprise Communications GmbH Version 1.0 Purpose This document describes new features, changes, and solved problems of BRICKware 7.5.4.

Mehr

DMS für besondere Anwendungen - Hochtemperatur-DMS

DMS für besondere Anwendungen - Hochtemperatur-DMS Hochtemperatur-DMS DMS für besondere Anwendungen - Hochtemperatur-DMS MERKMALE Einsatzbereich bis 115 C Freigitter-DMS aus Kanthal-Legierung zur Installation mit Keramikklebern Linear-DMS und T-Rosetten

Mehr

Time Delay Undervoltage Module for use with Undervoltage Release in Eaton Circuit Breakers

Time Delay Undervoltage Module for use with Undervoltage Release in Eaton Circuit Breakers Instructional Leaflet IL5721B33H03 Effective December 2010 Supersedes IL5721B33H02 Time Delay Undervoltage Module for use with Undervoltage Release in Eaton Circuit Breakers 120VAC CAT. #MTD 120V CAT.

Mehr

Installation and Removal Instructions for Series NRX Cassette Cell Switch

Installation and Removal Instructions for Series NRX Cassette Cell Switch Installation and Removal Instructions for Series NRX Cassette Cell Switch Instructions apply to: Effective April 2014 Supercedes August 2013 Series NRX Series NRX, Type RF Frame IEC, IZMX40 WARNING (1)

Mehr

Installation and Removal Instructions for Series NRX CES Interlock Kit

Installation and Removal Instructions for Series NRX CES Interlock Kit effective October 2012 Series NRX Installation and Removal Instructions for Series NRX CES Interlock Kit Instructions apply to: Series NRX, Type NF Frame ANSI, UL1066, UL489 / IEC, IZMX16, IZM91 Series

Mehr

User Manual Bedienungsanleitung. www.snom.com. snom Wireless Headset Adapter snom Schnurlos-Headset-Adapter. English. Deutsch

User Manual Bedienungsanleitung. www.snom.com. snom Wireless Headset Adapter snom Schnurlos-Headset-Adapter. English. Deutsch English snom Wireless Headset Adapter snom Schnurlos-Headset-Adapter Deutsch User Manual Bedienungsanleitung 2007 snom technology AG All rights reserved. Version 1.00 www.snom.com English snom Wireless

Mehr

com.tom PORTAL Registrierung

com.tom PORTAL Registrierung com.tom PORTAL Registrierung Copyright 2000-2010 Beck IPC GmbH Page 1 of 6 TABLE OF CONTENTS 1 AUFGABE... 3 2 DEFINITIONEN... 3 3 PRODUKTE... 3 4 REGISTRIERUNG... 3 5 PROJEKT-REGISTRIERUNG... 4 5.1 PROJEKT...

Mehr

INSTALLATION AND OPERATING INSTRUCTIONS FOR LPS203-M LPS203-M 操 作 指 示

INSTALLATION AND OPERATING INSTRUCTIONS FOR LPS203-M LPS203-M 操 作 指 示 BEDIENUNGSANLEITUNG To comply with the published safety standards, the following must be observed when using this power supply. Um den zur Zeit gültigen Sicherheitsbestimmungen zu genügen, müssen die nachstehenden

Mehr

Montageanweisung für Serie NRX Mechanische 3-Wege Verriegelung für Ausfahrtechnik

Montageanweisung für Serie NRX Mechanische 3-Wege Verriegelung für Ausfahrtechnik Serie NRX Die Montageanweisung ist für folgende Baugrößen gültig: Serie NRX, Typ RF Baugröße IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES PERSONAL

Mehr

Circuit Breaker Accessory Zubehör für Leistungsschalter

Circuit Breaker Accessory Zubehör für Leistungsschalter s Circuit Breaker Accessory Zubehör für Leistungsschalter Lifting Device Krantraverse Catalog No. / Bestell-Nr.: -C-90-0 HINWEIS Das Zubehör ist verwendbar für die folgenden Geräte vom Siemens Typ WL leistungsschalter:

Mehr

Word-CRM-Upload-Button. User manual

Word-CRM-Upload-Button. User manual Word-CRM-Upload-Button User manual Word-CRM-Upload for MS CRM 2011 Content 1. Preface... 3 2. Installation... 4 2.1. Requirements... 4 2.1.1. Clients... 4 2.2. Installation guidelines... 5 2.2.1. Client...

Mehr

Wie Programm Neighborhood Agent mit Secure Gateway konfigurieren. von Stefan Müri

Wie Programm Neighborhood Agent mit Secure Gateway konfigurieren. von Stefan Müri Wie Programm Neighborhood Agent mit von Stefan Müri Notice The information in this publication is subject to change without notice. THIS PUBLICATION IS PROVIDED AS IS WITHOUT WARRANTIES OF ANY KIND, EXPRESS

Mehr

p^db=`oj===pìééçêíáåñçêã~íáçå=

p^db=`oj===pìééçêíáåñçêã~íáçå= p^db=`oj===pìééçêíáåñçêã~íáçå= How to Disable User Account Control (UAC) in Windows Vista You are attempting to install or uninstall ACT! when Windows does not allow you access to needed files or folders.

Mehr

Outdoor-Tasche. Operating Instructions Bedienungsanleitung GB D

Outdoor-Tasche. Operating Instructions Bedienungsanleitung GB D 00 181243 Outdoor Case Outdoor-Tasche Splish Splash Operating Instructions Bedienungsanleitung GB D A B C D OPEN G Operating instruction 1. Important Notes Children are not permitted to play with the device.

Mehr

Montageanweisung für Serie NRX Mechanische 2-Wege Verriegelung für Ausfahrtechnik

Montageanweisung für Serie NRX Mechanische 2-Wege Verriegelung für Ausfahrtechnik Serie NRX Ausfahrtechnik Die Montageanweisung ist für folgende Baugrößen gültig: Serie NRX, Typ RF Baugröße IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES

Mehr

p^db=`oj===pìééçêíáåñçêã~íáçå=

p^db=`oj===pìééçêíáåñçêã~íáçå= p^db=`oj===pìééçêíáåñçêã~íáçå= Error: "Could not connect to the SQL Server Instance" or "Failed to open a connection to the database." When you attempt to launch ACT! by Sage or ACT by Sage Premium for

Mehr

RS232-Verbindung, RXU10 Herstellen einer RS232-Verbindung zwischen PC und Messgerät oder Modem und Messgerät

RS232-Verbindung, RXU10 Herstellen einer RS232-Verbindung zwischen PC und Messgerät oder Modem und Messgerät Betriebsanleitung RS232-Verbindung, RXU10 Herstellen einer RS232-Verbindung zwischen PC und Messgerät oder Modem und Messgerät ä 2 Operating Instructions RS232 Connection, RXU10 Setting up an RS232 connection

Mehr

Thule Excellence XT Instructions

Thule Excellence XT Instructions Thule Excellence XT Instructions 3DF/8.W35.2013 1801814100 Instructions Security x1 x1 x1 m x3 x1 x2 1 Max 80 mm Min 18 mm Max 30 mm Min 555 mm Max 935 mm Max 80 mm Min 18 mm Max 30 mm Min. 800 mm i Thule

Mehr

(825M) 2-Draht-Sender

(825M) 2-Draht-Sender Kamera SKS Bussystem 300004 (825M) 2-Draht-Sender 1. Installation Gefahr für Personen durch einen elektrischen Schlag. Verbrennungsgefahr, Geräteschäden und Fehlfunktionen. Bei der Installation sind die

Mehr

Umschaltadapter/ Changeover / Trennadapter Disconnection Adapter für LSA-PLUS NT for LSA-PLUS NT. Montageanweisung Mounting Instructions

Umschaltadapter/ Changeover / Trennadapter Disconnection Adapter für LSA-PLUS NT for LSA-PLUS NT. Montageanweisung Mounting Instructions Umschaltadapter/ Changeover / Trennadapter Disconnection Adapter für LSA-PLUS NT for LSA-PLUS NT Montageanweisung Mounting Instructions Der Umschalter dient zum unterbrechungsfreien Umschalten von Installations-drähten

Mehr

Aufbaudose mit Schalter Spacing box with switch. Montageanleitung mounting instructions

Aufbaudose mit Schalter Spacing box with switch. Montageanleitung mounting instructions Aufbaudose mit Schalter Spacing box with switch Montageanleitung mounting instructions body head Aufbaudose mit Schalter Montageanleitung S. 2 mounting instructions p. 9 $ 0.2m Sicherheitshinweise Die

Mehr

Montageanweisung für Series NRX Einschaltmagnet, Meldeschalter Einschaltbereit und Motorantrieb

Montageanweisung für Series NRX Einschaltmagnet, Meldeschalter Einschaltbereit und Motorantrieb Serie NRX Montageanweisung für Series NRX Die Montageanweisung ist für folgende Baugrößen gültig: Serie NRX, Type NF Baugröße ANSI, UL1066, UL489 / IEC, IZMX16, IZM91 Serie NRX, Type RF Baugröße, IEC,

Mehr

Electromagnetic Flowmeter FXE4000-DE43F

Electromagnetic Flowmeter FXE4000-DE43F Pos: 2 /Grid-Layout/Titelblätter/Ersatzteilblätter/Durchfluss/FXE4000-DE43F @ 65\mod_1350460748604_3101.docx @ 523546 @ @ 1 === Ende der Liste für Textmarke Cover === Spare Parts List SPL/FXE4000-DE43F-EN

Mehr

Level 2 German, 2013

Level 2 German, 2013 91126 911260 2SUPERVISOR S Level 2 German, 2013 91126 Demonstrate understanding of a variety of written and / or visual German text(s) on familiar matters 9.30 am Monday 11 November 2013 Credits: Five

Mehr

Patentrelevante Aspekte der GPLv2/LGPLv2

Patentrelevante Aspekte der GPLv2/LGPLv2 Patentrelevante Aspekte der GPLv2/LGPLv2 von RA Dr. Till Jaeger OSADL Seminar on Software Patents and Open Source Licensing, Berlin, 6./7. November 2008 Agenda 1. Regelungen der GPLv2 zu Patenten 2. Implizite

Mehr

Lukas Hydraulik GmbH Weinstraße 39 D Erlangen. Mr. Sauerbier. Lukas Hydraulik GmbH Weinstraße 39 D Erlangen. edraulic rescue equipment

Lukas Hydraulik GmbH Weinstraße 39 D Erlangen. Mr. Sauerbier. Lukas Hydraulik GmbH Weinstraße 39 D Erlangen. edraulic rescue equipment Technical Report No. 028-7130 95685-050 of 22.02.2017 Client: Lukas Hydraulik GmbH Weinstraße 39 D-91058 Erlangen Mr. Sauerbier Manufacturing location: Lukas Hydraulik GmbH Weinstraße 39 D-91058 Erlangen

Mehr

Hazards and measures against hazards by implementation of safe pneumatic circuits

Hazards and measures against hazards by implementation of safe pneumatic circuits Application of EN ISO 13849-1 in electro-pneumatic control systems Hazards and measures against hazards by implementation of safe pneumatic circuits These examples of switching circuits are offered free

Mehr

Open-Source-Software core_cm3.h

Open-Source-Software core_cm3.h Open-Source-Software Bei diesem Bosch Smart Home Produkt wird Open-Source-Software eingesetzt. Nachfolgend finden Sie die Lizenzinformationen zu den eingesetzten Komponenten. core_cm3.h Copyright (C) 2009-2013

Mehr

Bewässerung von Gewächshauspflanzen / Irrigation system for greenhouse plants

Bewässerung von Gewächshauspflanzen / Irrigation system for greenhouse plants Bewässerung von Gewächshauspflanzen / Irrigation system for greenhouse plants I2 I I1 I Minimal Wert Minimum Value Maximal Wert Maximum Value S R Par B004 RS B001 & Q1 Q Pflanzen Typ1 Plant type 1 I4 I

Mehr

Montageanweisung für Serie NRX Kassettenverriegelung

Montageanweisung für Serie NRX Kassettenverriegelung Die Montageanweisung ist für folgende Baugrößen gültig Serie NRX Serie NRX, Typ RF Baureihe IEC, IZMX40 WARNUNG (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES PERSONAL

Mehr

ATEX-Check list. Compiled by: Date: Signature: Acceptable practice at the determination of flash point: Closed cup according to ISO 2719

ATEX-Check list. Compiled by: Date: Signature: Acceptable practice at the determination of flash point: Closed cup according to ISO 2719 Fire and explosion hazard ATEX 137 1999/92/EG und ATEX 95 2014/34/EU Danger assessment and determination of explosion protection zone for the test space as well as the installation site ATEX-Check list

Mehr

Test Report. Test of resitance to inertia effects of Zirkona Backwall. Sled Test (Frontal Impact) 20 g / 30 ms

Test Report. Test of resitance to inertia effects of Zirkona Backwall. Sled Test (Frontal Impact) 20 g / 30 ms Test Report Test of resitance to inertia effects of Zirkona Backwall Sled Test (Frontal Impact) 20 g / 30 ms This report serves solely as a documentation of test results. 93XS0002-00_TdC.doc Page 1 1.

Mehr

Newest Generation of the BS2 Corrosion/Warning and Measurement System

Newest Generation of the BS2 Corrosion/Warning and Measurement System Newest Generation of the BS2 Corrosion/Warning and Measurement System BS2 System Description: BS2 CorroDec 2G is a cable and energyless system module range for detecting corrosion, humidity and prevailing

Mehr

MediaBoxXT 4.0. Einfache Erstellung von Postscript-Dateien mit QuarkXPress. JoLauterbach Software GmbH Stolzingstraße 4a 95445 Bayreuth Germany

MediaBoxXT 4.0. Einfache Erstellung von Postscript-Dateien mit QuarkXPress. JoLauterbach Software GmbH Stolzingstraße 4a 95445 Bayreuth Germany MediaBoxXT 4.0 Einfache Erstellung von Postscript-Dateien mit QuarkXPress JoLauterbach Software GmbH Stolzingstraße 4a 95445 Bayreuth Germany Telefon: 0921-730 3363 Fax: 0921-730 3394 Internet: email:

Mehr

Umrüstung von SMA Wechselrichtern nach SysStabV Bernd Lamskemper

Umrüstung von SMA Wechselrichtern nach SysStabV Bernd Lamskemper Umrüstung von SMA Wechselrichtern nach SysStabV Bernd Lamskemper Disclaimer IMPORTANT LEGAL NOTICE This presentation does not constitute or form part of, and should not be construed as, an offer or invitation

Mehr

Exercise (Part XI) Anastasia Mochalova, Lehrstuhl für ABWL und Wirtschaftsinformatik, Kath. Universität Eichstätt-Ingolstadt 1

Exercise (Part XI) Anastasia Mochalova, Lehrstuhl für ABWL und Wirtschaftsinformatik, Kath. Universität Eichstätt-Ingolstadt 1 Exercise (Part XI) Notes: The exercise is based on Microsoft Dynamics CRM Online. For all screenshots: Copyright Microsoft Corporation. The sign ## is you personal number to be used in all exercises. All

Mehr

TomTom WEBFLEET Tachograph

TomTom WEBFLEET Tachograph TomTom WEBFLEET Tachograph Installation TG, 17.06.2013 Terms & Conditions Customers can sign-up for WEBFLEET Tachograph Management using the additional services form. Remote download Price: NAT: 9,90.-/EU:

Mehr

2. For Entity concept use the appropriate parameters from above to ensure the following: V t or V OC V max

2. For Entity concept use the appropriate parameters from above to ensure the following: V t or V OC V max Class I, II, III, Div. 1, Group A - G or Class I, Zone 0, Group IIC/IIB Hazardous Locations Nonhazardous or Class I, Div. 2, Group A, B, C, D or Class I, Zone 2, Group IIC Hazardous Locations The copying,

Mehr

POST MARKET CLINICAL FOLLOW UP

POST MARKET CLINICAL FOLLOW UP POST MARKET CLINICAL FOLLOW UP (MEDDEV 2.12-2 May 2004) Dr. med. Christian Schübel 2007/47/EG Änderungen Klin. Bewertung Historie: CETF Report (2000) Qualität der klinischen Daten zu schlecht Zu wenige

Mehr

Parameter-Updatesoftware PF-12 Plus

Parameter-Updatesoftware PF-12 Plus Parameter-Updatesoftware PF-12 Plus Mai / May 2015 Inhalt 1. Durchführung des Parameter-Updates... 2 2. Kontakt... 6 Content 1. Performance of the parameter-update... 4 2. Contact... 6 1. Durchführung

Mehr

Nichttechnische Aspekte Hochverfügbarer Systeme

Nichttechnische Aspekte Hochverfügbarer Systeme Nichttechnische Aspekte Hochverfügbarer Systeme Kai Dupke Senior Product Manager SUSE Linux Enterprise kdupke@novell.com GUUG Frühjahrsfachgespräch 2011 Weimar Hochverfügbarkeit Basis für Geschäftsprozesse

Mehr

Wirtschaftsstandort. Augsburg. Dr. Marcus Cieleback, Group Head of Research, PATRIZIA Immobilien AG. 27. Juni PATRIZIA Immobilien AG

Wirtschaftsstandort. Augsburg. Dr. Marcus Cieleback, Group Head of Research, PATRIZIA Immobilien AG. 27. Juni PATRIZIA Immobilien AG Wirtschaftsstandort Augsburg Dr. Marcus Cieleback, Group Head of Research, PATRIZIA Immobilien AG 27. Juni 2016 PATRIZIA Immobilien AG PATRIZIA Bürohaus Fuggerstraße 26 86150 Augsburg T +49 821 50910-000

Mehr

Fitting Instructions for DG0017 BK Downpipe Grille BMW F800GT 2013

Fitting Instructions for DG0017 BK Downpipe Grille BMW F800GT 2013 Fitting Instructions for DG0017 BK Downpipe Grille BMW F800GT 2013 In This Kit There Should Be 1 x Downpipe Grille (DG0017) 2 x M5 Nyloc nuts PICTURE 1 PICTURE 2 PICTURE 3 PICTURE 4 1 PICTURE 5 PICTURE

Mehr

Funktionsbeschreibung/ Montageanweisung Steuermodul DSM 400 für Dunstabzugshaube DA 6000 W

Funktionsbeschreibung/ Montageanweisung Steuermodul DSM 400 für Dunstabzugshaube DA 6000 W Funktionsbeschreibung/ Montageanweisung Steuermodul DSM 400 für Dunstabzugshaube DA 6000 W Operation/Installation Control module DSM 400 for Cooker Hood DA 6000 W de, en M.-Nr. 09 165 660 Inhalt/Contents

Mehr

Encoder series / Drehgeber-Serie 500

Encoder series / Drehgeber-Serie 500 Encoder series / Drehgeber-Serie 500 Leine& Linde AB T +46 152 265 00 F +46 152 265 05 info@leinelinde.se www.leinelinde.com Mounting instructions / Montageanleitung 773562-01, ver. 1.0 RISK OF DAMAGE

Mehr

Password Management. Password Management Guide MF-POS 8

Password Management. Password Management Guide MF-POS 8 Password Management Password Management Guide MF-POS 8 MF-POS8 Einleitung Dieses Dokument beschreibt die Passwortverwaltung des Kassensystems MF-POS 8. Dabei wird zwischen einem Kellner und einem Verwaltungsbenutzer

Mehr

Technische Mitteilung / Service Bulletin

Technische Mitteilung / Service Bulletin Betrifft: Subject: Betroffenes Luftfahrtgerät: Type affected: Betroffene Geräte-Nr.: Models affected: Einstufung: Classification: Dringlichkeit: Accomplishment: Grund: Reason: Circuit Breaker Schaltungsänderung

Mehr

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005

Anlage zur Akkreditierungsurkunde D-PL nach DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Anlage zur Akkreditierungsurkunde D-PL-11055-09-00 nach DIN EN ISO/IEC 17025:2005 Gültigkeitsdauer: 09.02.27 bis 18.10.2020 Ausstellungsdatum: 09.02.27 Urkundeninhaber:

Mehr

Technische Mitteilung / Service Bulletin. PRIORITY 1 Safety

Technische Mitteilung / Service Bulletin. PRIORITY 1 Safety Platanenstrasse 4 Fax: +49 37204 696-292 TM TAE 25-005 P; Rev. 3 Technische Mitteilung / Service Bulletin PRIORITY Safety Technische Mitteilung Nr. / Datum: Service Bulletin No. / Date: TM TAE 25-005 P,

Mehr

1. Januar Quellen:

1. Januar Quellen: WHITEPAPER Einsatz von Murrelektronik MICO-Modulen für die Realisierung eines Low-Voltage Limited Energy Circuits in Industrial Control Panels (Steuer- und Schaltschränken) nach UL508A 1. Januar 2014 Quellen:

Mehr

Disclaimer SAP SE or an SAP affiliate company. All rights reserved. Public

Disclaimer SAP SE or an SAP affiliate company. All rights reserved. Public Disclaimer Die Informationen in dieser Präsentation sind vertraulich und urheberrechtlich geschützt und dürfen nicht ohne Genehmigung von SAP offengelegt werden. Diese Präsentation unterliegt weder Ihrem

Mehr

SERVICE INFORMATION NO. SI D4-138

SERVICE INFORMATION NO. SI D4-138 Diamond Aircraft Industries GmbH N.A. Otto-Straße 5 A-2700 Wiener Neustadt Austria DAI SI D-38 Page of 8-Jun-200 FT SERVICE INFORMATION NO. SI D-38 NOTE: SI s are used only: ) To distribute infmation from

Mehr

1. General information... 2 2. Login... 2 3. Home... 3 4. Current applications... 3

1. General information... 2 2. Login... 2 3. Home... 3 4. Current applications... 3 User Manual for Marketing Authorisation and Lifecycle Management of Medicines Inhalt: User Manual for Marketing Authorisation and Lifecycle Management of Medicines... 1 1. General information... 2 2. Login...

Mehr

Open-Source-Software

Open-Source-Software Open-Source-Software Bei diesem Bosch Smart Home Produkt wird Open-Source-Software eingesetzt. Nachfolgend finden Sie die Lizenzinformationen zu den eingesetzten Komponenten. core_cm3.h Copyright (C) 2009-2013

Mehr

Diese Produktinformation enthält neueste Informationen bzw. ergänzt die Angaben im Getting Started und im elektronischen Handbuch.

Diese Produktinformation enthält neueste Informationen bzw. ergänzt die Angaben im Getting Started und im elektronischen Handbuch. SIMATIC A5E00148511 01/2002 Box PC 840 Rack PC 840 mit Gleichspannungs-Stromversorgung (24V DC) with DC power supply (24V DC) Produktinformation Product Information Diese Produktinformation enthält neueste

Mehr

SmartClass Firmware-Update Vorgehensweise

SmartClass Firmware-Update Vorgehensweise Benutzeranweisungen SmartClass Firmware-Update Vorgehensweise 2008.01 (V 1.x.x) Deutsch Please direct all enquiries to your local JDSU sales company. The addresses can be found at: www.jdsu.com/tm-contacts

Mehr

i500 Sicherheitsmodul I5MASA000 I5MASA000 safety module Montageanleitung Mounting Instructions

i500 Sicherheitsmodul I5MASA000 I5MASA000 safety module Montageanleitung Mounting Instructions i500 Sicherheitsmodul I5MASA000 Montageanleitung I5MASA000 safety module Mounting Instructions Allgemeines Erst lesen, dann beginnen 1 1 Allgemeines 1.1 Erst lesen, dann beginnen Lesen Sie vor der Installation

Mehr

Kuhnke Technical Data. Contact Details

Kuhnke Technical Data. Contact Details Kuhnke Technical Data The following page(s) are extracted from multi-page Kuhnke product catalogues or CDROMs and any page number shown is relevant to the original document. The PDF sheets here may have

Mehr

mobilcom-debitel SmartHome Schnell-Start-Anleitung Quick Start Guide

mobilcom-debitel SmartHome Schnell-Start-Anleitung Quick Start Guide mobilcom-debitel SmartHome Schnell-Start-Anleitung Quick Start Guide 1. Cube anschließen 1. Connect Cube n Schließen Sie den Cube an die Stromversorgung an. n Legen Sie die Batterien polungsrichtig in

Mehr

Der Schutz-Garant. Das 1x1 des Kühlerschutzes

Der Schutz-Garant. Das 1x1 des Kühlerschutzes Headline Der Schutz-Garant. Das 1x1 des Kühlerschutzes Wie funktioniert das Kühlsystem? Das Grundprinzip ist einfach: 1/3 der im Motor erzeugten Energie wird in Form von Wärme vom Kühlmittelgemisch zum

Mehr

Notice: All mentioned inventors have to sign the Report of Invention (see page 3)!!!

Notice: All mentioned inventors have to sign the Report of Invention (see page 3)!!! REPORT OF INVENTION Please send a copy to An die Abteilung Technologietransfer der Universität/Hochschule An die Technologie-Lizenz-Büro (TLB) der Baden-Württembergischen Hochschulen GmbH Ettlinger Straße

Mehr

Exercise (Part V) Anastasia Mochalova, Lehrstuhl für ABWL und Wirtschaftsinformatik, Kath. Universität Eichstätt-Ingolstadt 1

Exercise (Part V) Anastasia Mochalova, Lehrstuhl für ABWL und Wirtschaftsinformatik, Kath. Universität Eichstätt-Ingolstadt 1 Exercise (Part V) Notes: The exercise is based on Microsoft Dynamics CRM Online. For all screenshots: Copyright Microsoft Corporation. The sign ## is you personal number to be used in all exercises. All

Mehr

Montageanleitung Installation Manual

Montageanleitung Installation Manual Montageanleitung Installation Manual Inventux X-Series Flachdach Flat Roof 2 Oelschläger Metalltechnik GmbH Hertzstr. 1-3 D-27318 Hoya Telefon: +49 (0) 4251 816 0 Telefax: +49 (0) 4251 816 81 Email: solar@oelschlaeger.de

Mehr

Device Component: - SIPLUS extreme ET 200MP IM PN ST TX RAIL Order Nr. 6AG2155-5AA00-4AB0. Breslauer Straße Fürth Deutschland

Device Component: - SIPLUS extreme ET 200MP IM PN ST TX RAIL Order Nr. 6AG2155-5AA00-4AB0. Breslauer Straße Fürth Deutschland Department: DF FA SE R&D CI Date: 15.04.2016 Device Component: - SIPLUS extreme ET 200MP IM 155-5 PN ST TX RAIL Order Nr. 6AG2155-5AA00-4AB0 IM 155-5 PN+Bus Connector Sitz der Gesellschaft: Berlin und

Mehr

Ölmess-Stäbe-Satz für Motor und Automatikgetriebe Mercedes-Benz

Ölmess-Stäbe-Satz für Motor und Automatikgetriebe Mercedes-Benz Anwendung Anwendungshinweis V2112 Ölmess-Stäbe-Satz für Motor und Automatikgetriebe Mercedes-Benz Mercedes liefert die unten aufgeführten Motoren-Codes werksseitig ohne Ölmessstäbe aus. Nach jedem Ölwechsel

Mehr

Level 2 German, 2015

Level 2 German, 2015 91126 911260 2SUPERVISOR S Level 2 German, 2015 91126 Demonstrate understanding of a variety of written and / or visual German text(s) on familiar matters 2.00 p.m. Friday 4 December 2015 Credits: Five

Mehr

Schaufensterbeleuchtung / Shop Window Lighting

Schaufensterbeleuchtung / Shop Window Lighting B003 No 1 + No 2 No 3 Mo..Fr 22:00h 01:00h Pulse=N 3 2 TEST - schalter TEST - switch EN - Schalter ON - switch / Shop Window Lighting B004 Trg R T B006 B002 B007 B001 B005 2 Lichtgruppe 1 Light group 1

Mehr

Industrial Communication

Industrial Communication Industrial Communication Betriebsanleitung (kompakt) Operating Instructions (Compact) A5E28893-3 Ausgabe / Release 9/27 ANT795-4MR (Omni-Antenne 2,4 / 5,25 / 5,8 GHz) ANT795-4MR (Omni Antenna 2.4 / 5.25

Mehr

Level 1 German, 2014

Level 1 German, 2014 90886 908860 1SUPERVISOR S Level 1 German, 2014 90886 Demonstrate understanding of a variety of German texts on areas of most immediate relevance 9.30 am Wednesday 26 November 2014 Credits: Five Achievement

Mehr

HiPath Cordless IP Einrichtung SIRA-Zugang. Administrator Documentation A31003-C1000-M100-2-A9

HiPath Cordless IP Einrichtung SIRA-Zugang. Administrator Documentation A31003-C1000-M100-2-A9 HiPath Cordless IP Einrichtung SIRA-Zugang Administrator Documentation A31003-C1000-M100-2-A9 Our Quality and Environmental Management Systems are implemented according to the requirements of the ISO9001

Mehr

Öffentlicher Deckungsstock

Öffentlicher Deckungsstock Öffentlicher Deckungsstock 30.06.2017 Deckungsstöcke Öffentlicher Deckungsstock Deckungsmasse nach Ländern EUR Milliarden (Nominal) 8,7 7,6 31.03.2017 / Gesamt: EUR 18,8 Mrd. 1 30.06.2017 / Gesamt: EUR

Mehr

Produktinformation Access-Gateway. Product information Access gateway AGW 670-0

Produktinformation Access-Gateway. Product information Access gateway AGW 670-0 Produktinformation Access-Gateway Product information Access gateway AGW 670-0 1 2 3 4 2 Deutsch Anwendung Access-Gateway zur physikalischen Trennung von 2 Netzwerken an einem Access-Server. Durch den

Mehr

Ölmess-Stäbe-Satz für Motor und Automatikgetriebe Mercedes-Benz

Ölmess-Stäbe-Satz für Motor und Automatikgetriebe Mercedes-Benz Anwendung Anwendungshinweis V2112 Ölmess-Stäbe-Satz für Motor und Automatikgetriebe Mercedes-Benz Mercedes liefert die unten aufgeführten Motoren-Codes werksseitig ohne Ölmessstäbe aus. Nach jedem Ölwechsel

Mehr

PELTIER-HOCHLEISTUNGSMODULE

PELTIER-HOCHLEISTUNGSMODULE Wolfgang Knap Gesellschaft m.b.h. & Co.KG A-113 Wien Lilienberggasse 13 Tel.: +43-1-43 8 12 Fax: +43-1-48 72 13 e-mail: info@knap.at http://www.knap.at PELTIER-HOCHLEISTUNGSMODULE Die Hochleistungsmodule

Mehr